Plan Review Notes
Plan Review Notes For Permit 15061203
Permit Number 15061203
Review Stop G
Sequence Number 1
Notes
Date Text
2015-07-15 05:48:261) SHOW THE LOCATION OF THE TANKLESS WATER ON THE FLOOR
 PLAN.THE PLANS SHOW A TANK TYPE WATER HEATER IN THE
 GARAGE. WHAT IS BEING INSTALLED, A TANKLESS WATER
 HEATER OR A TANK TYPE? CLARIFY.WPB AMEND. TO FBC
 SEC.107.2.1.
 2) IF THE TANK TYPE WATER HEATER IN THE GARAGE IS
 REMAINING, IT SHALL BE PROTECTED FROM VEHICLE IMPACT
 DAMAGE,SUBMIT DETAILS AS TO THE METHOD OF
 PROTECTION.WPB AMEND. TO FBC SEC. 107.2.1.
 3) THE GAS RISER SHOWS A GAS GRILL ON IT BUT IT IS NOT
 SHOWN ANYWHERE ON THE PLANS. CLARIFY.
 5) SHOW THE LOCATION OF THE GAS METER ON THE PLANS. WPB
 AMEND. TO FBC SEC. 107.2.1.
 6 THE GAS INSTALLATION SHALL BE DONE UNDER A SEPARATE
 PERMIT. TWO COPIES OF MANUF. SPECS. FOR ALL QAS
 APPLIANCES SHALL BE SUBMITTED AT TIME OF GAS
 APPLICATION SUBMITTAL ALONG WITH VENTING DETAILS AND
 COMBUSTION AIR CALCULATIONS AND OTHER DETAILS AS
 REQUIRED BY THE CODE.
 7) SHT. P-1 INDICATES THE GAS PIPING WILL BE METALLIC
 PIPE. METALLIC PIPE CANNOT BE INSTALLED UNDERGROUND PER
 2012 FBC- RESIDENTIAL, SEC. G 2415.9, G2415.9.1.
 INDICATE THE TYPE OF PIPING TO BE INSTALLED FOR THE
 POOL HEATER,
  