| Plan Review Notes For Permit 15061203 |
| Permit Number |
15061203 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-07-15 05:48:26 | 1) SHOW THE LOCATION OF THE TANKLESS WATER ON THE FLOOR | | | PLAN.THE PLANS SHOW A TANK TYPE WATER HEATER IN THE | | | GARAGE. WHAT IS BEING INSTALLED, A TANKLESS WATER | | | HEATER OR A TANK TYPE? CLARIFY.WPB AMEND. TO FBC | | | SEC.107.2.1. | | | 2) IF THE TANK TYPE WATER HEATER IN THE GARAGE IS | | | REMAINING, IT SHALL BE PROTECTED FROM VEHICLE IMPACT | | | DAMAGE,SUBMIT DETAILS AS TO THE METHOD OF | | | PROTECTION.WPB AMEND. TO FBC SEC. 107.2.1. | | | 3) THE GAS RISER SHOWS A GAS GRILL ON IT BUT IT IS NOT | | | SHOWN ANYWHERE ON THE PLANS. CLARIFY. | | | 5) SHOW THE LOCATION OF THE GAS METER ON THE PLANS. WPB | | | AMEND. TO FBC SEC. 107.2.1. | | | 6 THE GAS INSTALLATION SHALL BE DONE UNDER A SEPARATE | | | PERMIT. TWO COPIES OF MANUF. SPECS. FOR ALL QAS | | | APPLIANCES SHALL BE SUBMITTED AT TIME OF GAS | | | APPLICATION SUBMITTAL ALONG WITH VENTING DETAILS AND | | | COMBUSTION AIR CALCULATIONS AND OTHER DETAILS AS | | | REQUIRED BY THE CODE. | | | 7) SHT. P-1 INDICATES THE GAS PIPING WILL BE METALLIC | | | PIPE. METALLIC PIPE CANNOT BE INSTALLED UNDERGROUND PER | | | 2012 FBC- RESIDENTIAL, SEC. G 2415.9, G2415.9.1. | | | INDICATE THE TYPE OF PIPING TO BE INSTALLED FOR THE | | | POOL HEATER, | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|