| 2015-07-29 18:25:19 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE |
| | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO |
| | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE |
| | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. |
| | |
| | 1. CORRECT DRAWING INDEX TO INCLUDE ELECTRICAL PAGE |
| | E-0. |
| | 2. CORRECT "ELECTRICAL NOTES" # 19 TO INCLUDE 36" FROM |
| | TIP OF PADDLE FAN BLADE. |
| | 3. NEC 250.94, THE RISER DIAGRAM IS MISSING THE |
| | REQUIRED INTER-SYSTEM BONDING TERMINAL. |
| | 4. THE WORD ?ROMEX? AS USED IN THIS NOTE IS TO IDENTIFY |
| | A TYPE OF CABLE. ROMEX IS A BRAND NAME AND NOT A TYPE |
| | OF CABLE, REFER TO CABLE TYPES ?NM?, ?NMC? OR ?NMS?. |
| | 5. THE LOAD CALCS AS SUBMITTED DID NOT MATCH WITH MY |
| | CALCULATION OF THE CONNECTED LOAD AS SUBMITTED. |
| | 6. FBC-B, PROVIDE THE SCALE USED ON THE DRAWING ALONG |
| | WITH THE COMPASS ?N? ON THE PLANS. |
| | 7. NEC 314.27(A), BOXES USED AT LUMINAIRE OR LAMPHOLDER |
| | OUTLETS IN A CEILING SHALL BE REQUIRED TO SUPPORT A |
| | LUMINAIRE WEIGHING A MINIMUM OF 50 LB. ADD THIS TO THE |
| | NOTES ON CEILING BOXES ON PAGE. |
| | 8. BATHROOM #3 IS MISSING THE REQUIRED GFCI OUTLET. |
| | 9. NEC 410.11, THE ATTIC LIGHT SHALL HAVE A GUARD |
| | AROUND THE LAMP. |
| | 10. FBC-E SECTION 404 HAS SPECIFIC LIGHTING |
| | REQUIREMENTS WHICH SHALL BE COMPLIED WITH. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU |
| | |