Plan Review Notes
Plan Review Notes For Permit 15061203
Permit Number 15061203
Review Stop E
Sequence Number 1
Notes
Date Text
2015-07-29 18:25:19PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
  
 1. CORRECT DRAWING INDEX TO INCLUDE ELECTRICAL PAGE
 E-0.
 2. CORRECT "ELECTRICAL NOTES" # 19 TO INCLUDE 36" FROM
 TIP OF PADDLE FAN BLADE.
 3. NEC 250.94, THE RISER DIAGRAM IS MISSING THE
 REQUIRED INTER-SYSTEM BONDING TERMINAL.
 4. THE WORD ?ROMEX? AS USED IN THIS NOTE IS TO IDENTIFY
 A TYPE OF CABLE. ROMEX IS A BRAND NAME AND NOT A TYPE
 OF CABLE, REFER TO CABLE TYPES ?NM?, ?NMC? OR ?NMS?.
 5. THE LOAD CALCS AS SUBMITTED DID NOT MATCH WITH MY
 CALCULATION OF THE CONNECTED LOAD AS SUBMITTED.
 6. FBC-B, PROVIDE THE SCALE USED ON THE DRAWING ALONG
 WITH THE COMPASS ?N? ON THE PLANS.
 7. NEC 314.27(A), BOXES USED AT LUMINAIRE OR LAMPHOLDER
 OUTLETS IN A CEILING SHALL BE REQUIRED TO SUPPORT A
 LUMINAIRE WEIGHING A MINIMUM OF 50 LB. ADD THIS TO THE
 NOTES ON CEILING BOXES ON PAGE.
 8. BATHROOM #3 IS MISSING THE REQUIRED GFCI OUTLET.
 9. NEC 410.11, THE ATTIC LIGHT SHALL HAVE A GUARD
 AROUND THE LAMP.
 10. FBC-E SECTION 404 HAS SPECIFIC LIGHTING
 REQUIREMENTS WHICH SHALL BE COMPLIED WITH.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  