2015-08-21 09:09:191ST REVIEW: FBC 2010 BUILDING
 PERMIT #15061203
 8/21/15
  
 1) SHEET CS1: PLEASE REVISE THE FLORIDA BUILDING CODE
 REFERENCE LISTED UNDER "CODES USED" TO INDICATE THE
 FLORIDA BUILDING CODE RESIDENTIAL- 2010. REFER TO
 SECTION R101.2.
 2) GEOTECHNICAL EVALUATION REQUIRED FOR CONSTRUCTION OF
 THE BUILDING. SUBMIT TWO COPIES OF A SOIL TEST AND
 REPORT SIGNED AND SEALED BY A FLORIDA LICENSED
 GEOTECHNICAL ENGINEER- SECTION R401.4 FBC-10
 RESIDENTIAL.
 3) PLEASE REVIEW SECTION R301 FBC-10 RESIDENTIAL AND
 PROVIDE THE WIND DESIGN CRITERIA ON THE PLAN:
 BASIC WIND SPEED PER FIGURE R301.2.(4),
 WIND SPEED CONVERSION IN ACCORDANCE WITH SECTION
 R301.2.1.3.
 EXPOSURE CATEGORY- R301.2.1.4.
 COMPONENTS AND CLADDING PRESSURES POSITIVE AND
 NEGATIVE- TABLE R301.2(2).
 HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENTS- TABLE
 R301.2(3).
 WINDLOADS- LATERAL AND UPLIFT PRESSURES- ON ROOFTOP
 STRUCTURES AND EQUIPMENT- SECTION R301.2.1.1.3
 4) S-0: SPECIFY THE PSI OF COLUMN, FILL CELL, AND BOND
 BEAM GROUT.
 5) S-1B: PLACE A NOTE INDICATING SUBTERRANEAN TERMITE
 PROTECTION (SOIL TREATMENT) WILL BE PROVIDED IN
 ACCORDANCE WITH R318 FBC-10 RESIDENTIAL.
 6) S-1B: THE SPACINGS OF THE #5 VERTICAL REINFORCEMENT
 BARS (REBAR) ON THE MAIN HOUSE AND GARAGE EXTERIOR
 MASONRY WALLS ARE EXCEEDING THE ALLOWABLE MAXIMUMS AS
 DETERMINED BY TABLE R609.3.3A-1. PLEASE REDUCE THE
 SPACING PER THE TABLE REQUIREMENTS.
 7) S-1B: PROVIDE STRUCTURAL DETAILS FOR THE ACCU PAD.
 8) S-4B: DETAIL 5/S4- SPECIFY PRESSURE TREATED FOR THE
 2X4 SLEEPER- R317.1
 9) S-4B: DETAIL 9/S4- INDICATE THE SPECIES, GRADE,
 SIZE, AND SPACING OF WOOD STUDS FOR THE GARAGE/LIVING
 COMMON WALL. SPECIFY PRESSURE TREATED FOR THE BOTTOM
 PLATE.
 10) S-4B: DETAIL 4/S4 & 5/S4- INDICATE THE TYPE OF
 WEATHER AND WATER RESISTANT FINISH TO BE ATTACHED TO
 THE WOOD FRAMED GABLE WALLS. REFER TO SECTION R703 AND
 R703.6 FOR EXTERIOR PLASTER (STUCCO), AND R703.6.3 FOR
 WATER-RESISTANT BARRIER MATERIAL. REVISE THE DETAIL
 ACCORDINGLY.
 11) REFER TO SECTION R301.1 AND ADDRESS ITEM #6 AS IT
 RELATES TO THE ROOF OVERHANG AND THE OPENING IN THE
 SUMMER KITCHEN WALL. INDICATE SEPARATION DISTANCES TO
 THE ADJACENT BUILDING.
 12) 2B: PLACE A NOTE IN THE PLAN INDICATING WHICH
 BATHROOM DOOR IS MEETING COMPLIANCE FOR THE REQUIRED
 29-INCH CLEAR OPENING PER SECTION R320.1.1.
 13) 9B: DETAIL 3- INDICATE THE TYPE, SIZE, AND SPACINGS
 OF THE 2X12 ANCHORS.
 14) 10B: DETAIL 3- REFER TO SECTION R401.3 AND SHOW THE
 MINIMUM GRADE FALL AWAY FROM THE FOUNDATION.
 15) PRODUCT APPROVALS AND MIAMI-DADE NOA'S: A) THE
 GARAGE DOOR PRODUCT APPROVAL FL 09174-R7 IS OUTDATED
 FOR 2010- PROVIDE TWO COPIES OF FL 09174-R9. B) ENTRY
 DOOR FL 8871.5-R4 IS OUTDATED FOR 2010- PROVIDE TWO
 COPIES OF FL 8871.5-R6. C) THE DESIGN PROFESSIONAL OF
 RECORD SHALL CIRCLE, HIGHLIGHT, OR OTHERWISE MARK ALL
 APPLICABLE DETAILS, NOTES, DESIGN PRESSURES, GLASS
 TYPES, ANCHORING SCHEDULES ETC. ON THE PRODUCT
 APPROVALS AND NOA'S FOR THE WINDOWS, SLIDER DOORS,
 ENTRY DOORS, AND TILE ROOFING. PLEASE SUBMIT PRODUCT
 APPROVALS FOR TILE UNDERLAYMENT AND FOAM ADHESIVE IF
 APPLICABLE TO THE TILE ROOF INSTALLATION.
 16) ENERGY FORM 405-10: A) SEE PAGE 2- DATA FOR GABLE
 ROOF AREA NOT INDICATED. B) PAGE 3- WOOD WINDOWS ARE
 LISTED HOWEVER THE NOA'S INDICATE ALUMINUM. D) COMPLETE
 THE CODE COMPLIANCE CHECKLIST ON PAGE #5.
  