| Notes |
| Date |
Text |
| 2015-07-01 18:57:57 | IN ADDITION TO THE TAMPER-RESISTANT DEVICE REQUIREMENT | | | OF NEC 406.11, THE FOLLOWING PROVISOS ARE ATTACHED TO | | | THIS PERMIT. | | | ELECTRICAL PROVISOS: | | | 1. PER FBC-R 315 YOU SHALL INSTALL A CO DETECTOR WITHIN | | | 10? OF THE DOORS TO EVERY SLEEPING ROOM. | | | 2. PER NFPA 72 SECTION 29.8.3.4(4) SMOKE DETECTORS | | | MOUNTED WITHIN 10? OF A COOKING APPLIANCE SHALL BE | | | RATED FOR SUCH; IF PHOTOELECTRIC WITHIN 20? SHALL BE | | | EQUIPPED W/A SILENCING MEANS. | | | 3. PER NFPA 72 SECTION 29.8.3.4(6) SMOKE DETECTORS | | | SHALL NOT BE INSTALLED WITHIN 3? FROM A DOOR TO A | | | BATHROOM CONTAINING A SHOWER OR TUB UNLESS LISTED FOR | | | SUCH. | | | 4. PER NEC 314.27 CEILING MOUNTED LUMINAIRE OUTLETS | | | SHALL BE LISTED TO SUPPORT 50# | | | 5. PER NEC 314.20 BOXES IN NON-COMBUSTIBLE WALLS MAY | | | SETBACK NO MORE THAN 1/8? FROM SURFACE AND FLUSH WITH | | | COMBUSTIBLE SURFACES. | | | |
|