Plan Review Notes
Plan Review Notes For Permit 15061181
Permit Number 15061181
Review Stop E
Sequence Number 2
Notes
Date Text
2015-10-23 09:35:53I TRIED TO RED-LINE THESE FOR THE CONTRACTOR IN ORDER
 TO ISSUE THE PERMIT, BUT LATER REALIZED THAT THIS HAD
 FAILED THE FIRE AND BLDG REVIEWS AND A PROVISO WOULD
 NOT HELP. I EMAILED JOE OF GLIDDENSPINA TO ADVISE HIM
 THE THE SITUATION.
 THE FOLLOWING ITEMS NEED TO BE CORRECTED ON THE
 DRAWINGS:
 1. THE LIGHT IN THE STORAGE AREA SHALL BE CONTROLLED
 VIA AN OCCUPANCY/MOTION SENSOR SWITCH RATHER THAN A
 STRAIGHT ON/OFF SWITCH SO THE LIGHT CAN'T BE LEFT ON
 UNINTENTIONALLY.
 2. THERE IS A SIGN OUTLET MISSING FROM A SECOND ENTRY
 DOOR AS EXPLAINED TO JOE.
2015-10-22 10:51:25I CALLED TO SPEAK W/THE DESIGN PROFESSIONAL ON TWO
 MINOR ITEMS NEEDING CORRECTION. I AM WILLING TO
 RED-LINE THE DRAWINGS AND GET THEM OUT AS LONG AS THE
 DP CONCURS WITH MY FINDINGS.