| Plan Review Notes For Permit 15061181 |
| Permit Number |
15061181 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-10-23 09:35:53 | I TRIED TO RED-LINE THESE FOR THE CONTRACTOR IN ORDER | | | TO ISSUE THE PERMIT, BUT LATER REALIZED THAT THIS HAD | | | FAILED THE FIRE AND BLDG REVIEWS AND A PROVISO WOULD | | | NOT HELP. I EMAILED JOE OF GLIDDENSPINA TO ADVISE HIM | | | THE THE SITUATION. | | | THE FOLLOWING ITEMS NEED TO BE CORRECTED ON THE | | | DRAWINGS: | | | 1. THE LIGHT IN THE STORAGE AREA SHALL BE CONTROLLED | | | VIA AN OCCUPANCY/MOTION SENSOR SWITCH RATHER THAN A | | | STRAIGHT ON/OFF SWITCH SO THE LIGHT CAN'T BE LEFT ON | | | UNINTENTIONALLY. | | | 2. THERE IS A SIGN OUTLET MISSING FROM A SECOND ENTRY | | | DOOR AS EXPLAINED TO JOE. | | 2015-10-22 10:51:25 | I CALLED TO SPEAK W/THE DESIGN PROFESSIONAL ON TWO | | | MINOR ITEMS NEEDING CORRECTION. I AM WILLING TO | | | RED-LINE THE DRAWINGS AND GET THEM OUT AS LONG AS THE | | | DP CONCURS WITH MY FINDINGS. |
|