Text |
| 2015-10-02 11:06:00 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15061181 |
| | ADD: 2403 S DIXIE HIGHWAY |
| | CONT: BUTLER CONSTRUCTION COMPANY |
| | TEL: (561)832-9700 |
| | E-MAIL: SBUTLERBUTLERCONSTRUCTIONUSA.COM |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | |
| | 2ND REVIEW |
| | DATE: FRI. OCT. 02/2015 |
| | ACTION: DENIED |
| | |
| | NOTE: THE MEZZANINE AS IT STANDS IS A CODE COMPLIANT |
| | MEZZANINE UNDER THE BUILDING CODE IT WAS BUILT |
| | UNDER1960-1961 SOUTHERN STANDARD BUILDING CODE. 402.4. |
| | MEZZANINE FLOORS SHALL NOT BE REGARDED AS A STORY |
| | UNLESS THEY EXCEED THIRTY-THREE AND ONE-THIRD (33 1/3) |
| | PER CENT OF THE AGGREGATE FLOOR AREA. THE CURRENT |
| | CODE2010 FBC-B 505.2 THE WORDING STATES THE ENCLOSED |
| | PORTION OF A ROOM SHALL NOT BE INCLUDED IN A |
| | DETERMINATION OF THE FLOOR AREA OF THE ROOM IN WHICH |
| | THE MEZZANINE IS LOCATED. |
| | |
| | AS PART OF THE INTERIOR DEMO PERMIT 800 SQ. FT. OF |
| | MEZZANINE FLOOR AREA WAS REMOVED FROM THE FLOOR AREA, |
| | THE MEZZANINE FLOOR WILL BE DEEMED CODE COMPLIANT UNDER |
| | THE 2010 FBC-EXISTING BUILDING 101.5 EXCEPTION SUBJECT |
| | TO THE APPROVAL OF THE BUILDING OFFICIAL, ALTERATIONS |
| | COMPLYING WITH THE LAWS IN EXISTENCE AT THE TIME THE |
| | BUILDING WAS BUILT. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1) COMPLIED. INTERIOR RENOVATION. |
| | 2) COMPLIED. MERCANTILE. |
| | 3) COMPLIED |
| | 4) SHEET A-2.0: |
| | 4A-C) COMPLIED |
| | 4D) 2ND REQUEST . PLEASE PROVIDE THE WIND DESIGN |
| | CRITERIA FOR THE ROOF TOP CURB: |
| | 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- |
| | CHAPTER 6 OF ASCE 7-10. |
| | |
| | 4D)(1)COMPLIED. THE BASIC WIND SPEED, VU, SHALL BE |
| | DETERMINED IN ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| | |
| | 4D)( 2) COMPLIED. AN IMPORTANCE FACTOR, FIGURE 1609 |
| | A-C, ASCE 7-10. |
| | |
| | 4D)( 3) COMPLIED. AN EXPOSURE CATEGORY SHALL BE |
| | DETERMINED IN ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| | |
| | 4D)(4) 2ND REQUEST. A HEIGHT AND EXPOSURE ADJUSTMENT |
| | COEFFICIENT, * SHALL BE DETERMINED FROM TABLE 1609.7.2. |
| | ASCE 7-10. |
| | |
| | 4D)(5)2ND REQUEST. COMPONENTS & CLADDING PRESSURES |
| | POSITIVE & NEGATIVE TABLE 1609.2(2) . NOTE IF THE |
| | PARAPET IS 3?-0? OR MORE AROUND THE PERMTER !!!! |
| | AFFECTS ROOF PRESSURES FOR ZONE 3. |
| | |
| | 4E) COMPLIED. |
| | 4F) 2ND REQUEST, DO NOT RECITE CODE, SHOW COMPLIANCE. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. SUCH |
| | DRAWINGS AND SPECIFICATIONS SHALL CONTAIN INFORMATION, |
| | IN THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF |
| | MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY |
| | WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE |
| | SPECIFIC, AND THE TECHNICAL CODES SHALL NOT BE CITED AS |
| | A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS |
| | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION. |
| | COMMENT FROM 1ST REVIEW. PLEASE ALSO SHOW COMPLIANCE |
| | WITH 2010 FBC-B 1013.5 GUARDS ON ROOFS FOR MECHANICAL |
| | EQUIPMENT/ 1013.6 ROOF ACCESS. |
| | |
| | 5) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A)-(C) COMPLIED. |
| | 2ND REQUEST. (D) ROOFING PRODUCTS AND ASSEMBLIES/ ROOF |
| | TOP CURBS ROOFING REPAIRS OF THE ROOF WILL NEED TO |
| | OCCUR WHERE THE NEW ROOF HATCH AND ROOF TOP CURB ARE |
| | INSTALLED . |
| | |
| | 6) COMPLIED. 2010 FBC 107.3.4.1 PRODUCT APPROVALS. |
| | THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE |
| | 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC |
| | |
| | 7) SHEET A-8.0, NEW COMMENT THE STAIR DETAIL OPEN TO |
| | THE 2ND FLOOR NOW SHOWS A NEW MODULAR SHELVING UNIT. |
| | THE 2010 FBC-B 1009.9.3 THERE SHALL BE NO STORAGE UNDER |
| | THE STAIR, UNLESS IN A 1 HOUR ENCLOSURE. PLEASE REVIEW |
| | THE 2012 IBC COMMENTARY, COMMENTARY SECTION STATES, THE |
| | STAIRWAY MUST BE PROTECTED FROM STORAGE UNDER IT, EVEN |
| | IF THE STAIR IS NOT REQUIRED TO BE ENCLOSED. |
| | |
| | 8A) 2ND REQUEST. SHEET A1.5 INDICATES ON THE MEZZANINE |
| | LEVEL THIS AREA IS TO BE A STORAGE. PLEASE SEE UNDER |
| | THE 2010 FBC-B TABLE 1607.1 STORAGE LIGHT 125 PSF OR |
| | HEAVY 250 PSF. |
| | SHEET A1.5COMMENT FROM 1ST REVIW.2010 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 106.1 LIVE LOADS POSTED. WHERE THE LIVE |
| | LOADS FOR WHICH EACH FLOOR OR PORTION THEREOF OF A |
| | COMMERCIAL OR INDUSTRIAL BUILDING IS OR HAS BEEN |
| | DESIGNED TO EXCEED 50 PSF (2.40 KN/M2), SUCH DESIGN |
| | LIVE LOADS SHALL BE CONSPICUOUSLY POSTED BY THE OWNER |
| | IN THAT PART OF EACH STORY IN WHICH THEY APPLY, USING |
| | DURABLE SIGNS. IT SHALL BE UNLAWFUL TO REMOVE OR DEFACE |
| | SUCH NOTICES. |
| | |
| | 8B) 2ND REQUEST. 106.2 ISSUANCE OF CERTIFICATE OF |
| | OCCUPANCY. A CERTIFICATE OF OCCUPANCY REQUIRED BY |
| | SECTION 111 SHALL NOT BE ISSUED UNTIL THE FLOOR LOAD |
| | SIGNS, REQUIRED BY SECTION 106.1, HAVE BEEN INSTALLED. |
| | |
| | 8C) 2ND REQUEST. 106.3 RESTRICTIONS ON LOADING. IT |
| | SHALL BE UNLAWFUL TO PLACE, OR CAUSE OR PERMIT TO BE |
| | PLACED, ON ANY FLOOR OR ROOF OF A BUILDING, STRUCTURE |
| | OR PORTION THEREOF, A LOAD GREATER THAN IS PERMITTED BY |
| | THIS CODE. |
| | |
| | 9) PLANS MAY REQUIRE REVIEW BY PALM BEACH COUNTY IMPACT |
| | FEE OFFICE. BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. |
| | THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION |
| | |
| | 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |