| Plan Review Notes For Permit 15061181 |
| Permit Number |
15061181 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-08-10 15:51:33 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS | | | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE | | | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO | | | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE | | | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. | | | 1. ELECTRICAL SUB PERMIT REQUIRRED | | | 2. GRD FLOOR LIGHTING NOT IN COMPLIANCE W/FBC-E | | | 3. GRD FLOOR MISSING EMERGENCY LIGHTING IN RESTROOMS, | | | OFFICE 105 & BREAK ROOM PER FBC=B 1006.2 | | | 4. GRD FLOOR MISSING THE SHOW WINDOW OUTLETS REQUIRED | | | IN NEC 210.62 | | | 5. GRD FLOOR MISSING THE SIGN OUTLET AS PER NEC 600.5 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | | | | THANK YOU | | | | | 2015-07-24 10:00:07 | | | | |
|