| 2015-07-24 07:42:07 | 2ND REVIEW: FBC 2010 MECHANICAL |
| | 7/24/15 |
| | |
| | 1) IN RESPONSE TO 1ST REVIEW COMMENT #5, ORBIT LABS HAS |
| | SUBMITTED LETTERS INDICATING MINIMAL LEVELS OF |
| | FLAMMABLE VAPORS, GAS, FUMES, MIST, AND DUSTS FROM THE |
| | CHEMICAL PROCESSES WILL BE EXHAUSTED THROUGH THE NEW |
| | CAPTURE HOOD SYSTEM. IN ORDER TO VERIFY COMPLIANCE WITH |
| | SECTION 510.2 FBC-10 MECHANICAL (WHICH OUTLINES THE |
| | PARAMETERS BY WHICH A HAZARDOUS EXHAUST SYSTEM IS |
| | REQUIRED), AND IN ACCORDANCE WITH SECTION 502.8, PLEASE |
| | SUBMIT MSDS SHEETS FOR THE CHEMICAL 2-PROPANOL, |
| | METHANOL, AND NIOTROGEN. INDICATE ON THE PLANS THE |
| | QUANTITIES OF EACH CHEMICAL BEING STORED IN THE |
| | FACILITY, AND HOW THE CHEMICALS ARE BEING STORED- ROOM, |
| | CLOSET, CABINET? THE ISSUE IS FURTHER EVIDENCE IS |
| | REQUIRED TO DETERMINE AN ACCURATE OCCUPANCY |
| | CLASSIFICATION FOR THE FACILITY, AND WHICH ASSOCIATED |
| | CODE REQUIREMENTS MUST BE ENFORCED- REFER TO TABLE |
| | 307.1(1) AND SECTION 414 FBC-10 BUILDING. |
| | 2) THE PLAN INDICATES A MANUALLY OPERATED RHEOSTAT WILL |
| | CONTROL THE EXHAUST FAN OPERATION- REFER TO SECTION |
| | 502.8.1.1 ITEM 3 AND PROVIDE EVIDENCE AS NOTED IN |
| | COMMENT #1 TO INDICATE CONTINUOUS OPERATION IS NOT |
| | APPLICABLE. |
| | 3) INDICATE ON THE PLAN THE TYPE OF AND GAGE OF EXHAUST |
| | DUCT MATERIAL TO BE CONNECTED TO THE EXHAUST HOOD, AND |
| | TO THE NITROGEN GENERATOR- REFER TO SECTION 510.8 |
| | FBC-10 MECHANICAL. |
| | 3) AS PREVIOUSLY REQUESTED, PROVIDE AN EQUIPMENT |
| | SCHEDULE AND AN EQUIPMENT FLOOR PLAN LAYOUT. IDENTIFY |
| | ALL EQUIPMENT ON THE PLAN AS EITHER NEW, EXISTING, OR |
| | FUTURE. |
| | 4) AS PREVIOUSLY REQUESTED, SUBMIT THE MIAMI-DADE NOA |
| | FOR THE AC ROOF STAND. |
| | 5) THE SUBMITTED ENERGY COMPLIANCE FORM DOES NOT |
| | INCLUDE THE ENERGY EFFICIENCY COMPLIANCE SUMMARY PAGES: |
| | 6) PLEASE NOTE THAT THE CITY OF WPB BUILDING DIVISION |
| | REQUIRES ALL COMPLIANCE DOCUMENTS, NOA'S, PRODUCT CUT |
| | SHEETS ETC. TO BE SUBMITTED IN DUPLICATE. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 561-805-6719 |
| | [email protected] |
| | |