| 2015-06-25 14:30:24 | 1ST REVIEW: FBC 2010 MECHANICAL |
| | |
| | 1) THE AC SIZING LOAD CALCULATIONS INDICATE 60775 |
| | BTU/HR FOR MISCELLANEOUS: PLEASE PROVIDE MORE SPECIFIC |
| | INFORMATION. IS THIS LOAD BEING GENERATED BY EQUIPMENT- |
| | EITHER NEW OR EXISTING? |
| | 2) SHEET S-1 AND THE STRUCTURAL CALCULATIONS INDICATE |
| | TWO NEW EXHAUST FANS, HOWEVER ONLY ONE IS NOTED AND |
| | SHOWN IN THE MECHANICAL PLANS: PLEASE CLARIFY. |
| | 3) CLARIFY HOW MAKE-UP AIR IS BEING PROVIDED FOR THE |
| | EXHAUST HOOD- EXISTING OR NEW SUPPLY? PROVIDE NOTES AND |
| | CALCULATIONS, AND DRAWINGS FOR ALL NEW INSTALLATIONS. |
| | 4) PLEASE PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN |
| | IDENTIFYING ALL NEW AND EXISTING EQUIPMENT IN THE LAB, |
| | INCLUDING THE PIECE OF EQUIPMENT THAT IS REQUIRING THE |
| | EXHAUST HOOD. |
| | 5) WHAT IS THE TYPE OF EXHAUST- REFERENCE SECTION |
| | 501.2.1 FBC-10 MECH. FOR OUTLET LOCATIONS, AND 510.2 |
| | FOR HAZARDOUS EXHAUST REQUIREMENTS. |
| | 6) SHEET A-1 SHOWS THE NEW AC AND FAN EQUIPMENT WITHIN |
| | 10 FT. OF THE ROOF EDGE WHICH REQUIRES EITHER A GUARD |
| | OR A MINIMUM 42' PARAPET WALL- SECTION 304.11. |
| | 7) PROVIDE A SUBMITTAL PACKAGE PREPARED BY THE DESIGN |
| | PROFESSIONAL OF RECORD THAT INCLUDES FL. PRODUCT |
| | APPROVALS AND/OR MIAMI-DADE NOA'S, AND PRODUCT DATA |
| | SHEETS FOR ALL NEW COMPONENTS OF THE AC AND EXHAUST |
| | SYSTEMS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 561-805-6719 |
| | [email protected] |
| | |