2015-06-24 17:00:071ST REVIEW: FBC 2010
  
 THE RISER DIAGRAM AS SHOWN IS NOT COMPLIANT.
  
 PROVIDE PER FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER
 WITH WIRE SIZES, CONDUIT DETAIL AND GROUNDING DETAIL
 AND PROPOSED CHANGES TO THE EXISTING RISER. PROVIDE
 OMPLETE LOAD CALCULATIONS, PANEL SCHEDULES AND PANEL
 LOCATIONS. NOTE THAT SMOKE DETECTORS ARE REQUIRED
 ADDITIONALLY INSIDE OF THE BEDROOMS, I BELIEVE YOU
 SHOWED CO DETECTORS INADVERTANTLY IN THE SLEEPING
 ROOMS.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER