| Plan Review Notes For Permit 15061110 |
| Permit Number |
15061110 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-06-24 17:00:07 | 1ST REVIEW: FBC 2010 | | | | | | THE RISER DIAGRAM AS SHOWN IS NOT COMPLIANT. | | | | | | PROVIDE PER FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER | | | WITH WIRE SIZES, CONDUIT DETAIL AND GROUNDING DETAIL | | | AND PROPOSED CHANGES TO THE EXISTING RISER. PROVIDE | | | OMPLETE LOAD CALCULATIONS, PANEL SCHEDULES AND PANEL | | | LOCATIONS. NOTE THAT SMOKE DETECTORS ARE REQUIRED | | | ADDITIONALLY INSIDE OF THE BEDROOMS, I BELIEVE YOU | | | SHOWED CO DETECTORS INADVERTANTLY IN THE SLEEPING | | | ROOMS. | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|