| Plan Review Notes For Permit 15061108 |
| Permit Number |
15061108 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-07-15 13:52:58 | THE FOLLOWING ITEMS SHALL BE CORRECTED AND THE PLANS | | | RESUBMITTED FOR ANOTHER REVIEW. | | | 1. THE INCORRECT CODE IS QUOTED. YOU QUOTE NFPA 72 2002 | | | EDITION IN ONE PLACE AND THEN THE 2007 EDITION ELSE | | | WHERE. | | | 2. PER NFPA 72 2007, SECTION 5.13.6, A PULL STATION IS | | | REQUIRED WITHIN 5' OF AN EXIT AT EVERY FLOOR. THIS | | | MEANS THE MEZZANINE LEVEL. | | | 3. PER FBC EACH ROOM SHALL BE LABELED | | | 4. PER FBC, DETAILS OF CEILING HEIGHT SHALL BE | | | PROVIDED. | | | 5. THOUGH THE VISUAL NOTIFICATION DEVICES APPEAR TO BE | | | WELL PLACED, THIS CAN CHANGE WITH THE ARRANGEMENT OF | | | SHELVING ETC. THIS SHALL BE DETERMINED AT THE FINAL | | | INSPECTION. |
|