| 2015-07-09 17:28:34 | 1ST REVIEW: FBC 2010 MECHANICAL | | | PERMIT #15061093 7/9/15 | | | | | | 1) PROVIDE ADDITIONAL FIRE DAMPER SPECIFICATIONS- | | | TYPES, FIRE RATINGS, AND HOW THEY WILL BE ACTUATED- SEE | | | SECTION 607, AND SUBMIT MANUFACTURER'S SPECIFICATIONS | | | REVIEWED AND APPROVED BY THE ENGINEER OF RECORD. | | | 2) PROVIDE ADDITIONAL DETAILS AND NOTES TO CLARIFY | | | WHERE THE RETURN AIR THROUGH THE 48X12 GRILL IS BEING | | | TRANSFERRED TO- ABOVE THE CORRIDOR CEILING INTO A RATED | | | PLENUM ENCLOSURE? | | | 3) AS NOTED ON SHEET M1.1, PLEASE SHOW WHERE THE | | | EXPOSED SPIRAL DUCTWORK IS TO BE INSTALLED IN THE | | | SPACE: THE LAYOUT PLAN APPEARS TO INDICATE ALL ABOVE | | | CEILING INSTALLATIONS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | |
|