| 2015-06-25 05:55:08 | 1)THE GAS PLAN IS UNACCEPTABLE. THERE ARE TOO MANY |
| | DEFICIENCIES TO LIST. COMPLY WITH ALL THE APPLICABLE |
| | REQUIREMENTS OF THE REQUIREMENTS FOR GAS PERMIT FORM |
| | THAT I HAVE ATTACHED TO THE PLANS. WPB AMEND. TO 2010 |
| | FBC SEC. 107.2.1. |
| | 2) THE CONTRACTOR IS LICENSED AS A CLASS "A" MECHANICAL |
| | CONTRACTOR. FLA. STATUTES 489.105 ( F ) DOES NOT ALLOW |
| | A CLASS "A" MECHANICAL CONTRACTOR TO RUN ANY GAS PIPE. |
| | A CLASS "A" CONTRACTOR MAY ONLY DISCONNECT AND |
| | RECONNECT CHANGEOUTS OF LP OR NATURAL GAS APPLIANCES. |
| | THIS PERMIT WILL NOT BE ISSUED TO THIS MECHANICAL |
| | CONTRACTOR. |
| | 3) GAS PERMIT APPLICATION REQUIREMENTS |
| | |
| | EFFECTIVE IMMEDIATELY THE FOLLOWING INFORMATION SHALL |
| | BE SHOWN ON ALL GAS DRAWINGS SUBMITTED FOR PERMITTING |
| | IN THE CITY OF WEST PALM BEACH: |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL |
| | CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER |
| | FBC-2010 FUEL GAS, SECS. 402.4.1, 402.4.2. |
| | |
| | 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL |
| | PIPE SIZES, AND THE EHD NUMBER OF CORRUGATED STAINLESS |
| | STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. |
| | |
| | 3. TYPE OF GAS, (LP OR NATURAL). |
| | |
| | 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON |
| | THE SYSTEM. REFER TO THE FBC-2010 FUEL GAS SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(35) |
| | |
| | 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, |
| | (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING |
| | AND/OR SYSTEM PER THE FBC-2010 FUEL GAS APPENDIX A ? |
| | USE OF CAPACITY SECTION A.3.1(4) & 2010 FUEL GAS CODE |
| | SEC. 402.4.1. |
| | |
| | 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE |
| | FBC-2010 FUEL GAS CODE SEC. 304 |
| | |
| | 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2010 |
| | FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2 |
| | PSI. |
| | |
| | 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND |
| | TERMINATION OF THE GAS VENTS PER FBC-2010 FUEL GAS CODE |
| | SEC. 502 THRU 505. |
| | |
| | 9. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL |
| | GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA |
| | 54, NFPA 58, AND FBC-2010 FUEL GAS SEC. 402.2 |
| | |
| | ANY QUESTIONS REGARDING THESE REQUIREMENTS MAY BE |
| | REFERRED TO: |
| | |
| | CHIEF PLUMBING INSPECTOR (561) 805-6692 |
| | |
| | |