| 2015-06-25 09:53:47 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE WIND UPLIFT ENHANCED FASTENING CALCULATIONS | | | SPECIFY PRODUCT APPROVAL FL14083-R7 SYSTEM NUMBER | | | SC-104 ON PAGE 16 OF 17. THE PRODUCT APPROVAL SUBMITTED | | | WAS FL14083-R8 AND SYSTEM NUMBER SC-116 ON PAGE 18 OF | | | 39 IS MARKED. SUBMIT MATCHING DOCUMENTS. FBC 107.2.1 | | | | | | 2) THE PRODUCT APPROVAL FOR A BILCO ROOF HATCH WITH A | | | DESIGN PRESSURE OF + OR - 70 PSF WAS SUBMITTED. PROVIDE | | | A ROOF PLAN THAT SHOWS THE LOCATION OF THE HATCH. BASED | | | ON THE ENGINEER'S ROOF FASTENING DOCUMENT AND THE | | | DESIGN PRESSURES FOR THIS HATCH, IT WILL HAVE TO BE | | | LOCATED IN ROOF ZONE 1. | | | | | | 3) CLARIFY THAT THE NEW BILCO HATCH IS THE REPLACEMENT | | | OF AN EXISTING ONE, WHICH CAN BE DONE WITH A CCC | | | LICENSE. OTHERWISE A GENERAL OR BUILDING CONTRACTOR | | | WILL BE REQUIRED TO INSTALL THE HATCH. FS 489.105(E) |
|