| 2015-09-17 16:21:45 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE |
| | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO |
| | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE |
| | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. |
| | |
| | 1. NEC 210.62 REQUIRES AT LEAST ONE RECEPTACLE OUTLET |
| | INSTALLED WITHIN 18? OF THE TOP OF A SHOW WINDOW FOR |
| | EVERY 12 LINEAR FOOT OR PORTION THEREOF. |
| | 2. NEC 600.5 REQUIRES THAT EVERY COMMERCIAL OCCUPANCY |
| | BE PROVIDED AT EACH PEDESTRIAN ENTRANCE TO THE SPACE A |
| | 20 AMP DEDICATED OUTLET FOR SIGNAGE OR OUTLINE LIGHTING |
| | PROVISIONS. |
| | 3. NEC 210.63 REQUIRES THAT THERE BE A 125 V 15 -20 AMP |
| | SERVICE OUTLET WITHIN 25? OF THE HVAC EQUIPMENT. |
| | 4. DESCRIBE AND PROVIDE SPEC SHEETS FOR THE |
| | APPARATUS/EQUIPMENT BEING CONNECTED TO THE PROPOSED 100 |
| | AMP 3? LOAD. |
| | 5. THE NOTES INCORRECTLY INDICATE THAT THE WORK SHALL |
| | BE AS PER THE 2007 FBC. THE CODE IN EFFECT FOR THIS |
| | PROJECT IS THE 2010 EDITION OF THE FBC. |
| | 6. ALL FIRE ALARM WORK SHALL BE PERFORMED UNDER A |
| | SEPARATE PERMIT AND SHOP DRAWINGS. |
| | 7. TEMP POWER FOR CONSTRUCTION SHALL REQUIRE A SEPARATE |
| | PERMIT. |
| | |
| | THOUGH THE MEP NARRATIVES WERE NOT AVAILABLE, THE ABOVE |
| | ITEMS NEED TO BE ADDRESSED FOR A SATISFACTORY |
| | ELECTRICAL REVIEW. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU |
| | |