Plan Review Notes
Plan Review Notes For Permit 15061025
Permit Number 15061025
Review Stop E
Sequence Number 1
Notes
Date Text
2015-06-24 16:57:596/24/2015
 PROJECT: AIM SUITE 150
 PERMIT#: 15061025
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) INDICATE THE SPECIFIC USE AND CONNECTION OF THE NEW
 100AMP 3PHASE 100AMP CIRCUIT . THE RISER DIAGRAM
 INDICATES A NEW DISCONNECT THEN CALLS OUT TO VERIFY
 FINAL CONNECTION TO EQUIPMENT. THE FLOOR PLAN INDICATES
 THE NEW 100AMP 3PHASE DISCONNECT CONNECTED TO A
 RECEPTACLE SYMBOL. PLEASE CLARIFY AND AND INDICATE WHAT
 EQUIPMENT THE NEW CIRCUIT IS FOR AND THE METHODS AND
 MATERIALS USED FOR THE FIANL CONNECTION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  