Plan Review Notes
Plan Review Notes For Permit 15061008
Permit Number 15061008
Review Stop E
Sequence Number 1
Notes
Date Text
2015-07-07 14:15:207/7/2015
 PROJECT: LOFTIN PLACE ACCESS CONTROL
 PERMIT#: 15061008
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) PROVIDE MANUFACTURER PRODUCT SUBMITTALS FOR
 EQUIPMENT, COMPONENTS AND CABLES PROPOSED TO BE
 INSTALLED.
  
 2) PROVIDE UL FIRE RATED ASSEMBLIES TO BE USED FOR
 PENATRATION OF FIRE RATED SURFACES.
  
 3) INDICATE THE LOCATION FOR ANY LINE VOLTAGE POWER
 SUPPLIES PROPOSED TO BE INSTALLED. THE INSTALLATION OF
 LINE VOLTAGE CONNECTIONS SHALL BE BY OTHERS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  