2015-08-17 12:25:391ST REVIEW: FBC 2010 MECHANICAL
 PERMIT #15061007
 8/17/15
  
 1) SUBMIT ACCA MANUAL J COOLING AND HEATING SIZING
 CALCULATIONS IN ACCORDANCE WITH SECTION 403.6.1 FBC-10
 ENERGY CONSERVATION.
 2) REFER TO SECTION 101.4.3 FBC-10 ENERGY CONSERVATION:
 ENERGY CALCULATIONS ARE REQUIRED FOR THE NEW ADDITION.
 PLEASE SUBMIT TWO COPIES OF FORM 402 (PRESCRIPTIVE
 COMPLIANCE) OR FORM 405 (PERFORMANCE COMPLIANCE)- SEE
 TABLE 103.2.1.
 3) THE ELECTRICAL PLAN INDICATES A BATH EXHAUST FAN.
 PLEASE SHOW THE FAN AND EXHAUST DUCT DETAILS ON THE
 MECHANICAL PLAN.
 4) PROVIDE DETAILS FOR INSTALLATION OF THE CONDENSER
 SLAB, AND TIE-DOWN ENGINEERING FOR ANCHORING THE UNIT
 TO THE SLAB- SECTION M1307.2.1 FBC-10 RESIDENTIAL.
 5) REFER TO SECTION 402.4.3 FBC-10 ENERGY CONSERVATION:
 NEW WOOD-BURNING FIREPLACES SHALL HAVE GASKETED DOORS
 AND OUTDOOR COMBUSTION AIR. PLEASE REVISE THE PLANS TO
 SHOW COMPLIANCE.
  