| 2015-08-17 12:25:39 | 1ST REVIEW: FBC 2010 MECHANICAL | | | PERMIT #15061007 | | | 8/17/15 | | | | | | 1) SUBMIT ACCA MANUAL J COOLING AND HEATING SIZING | | | CALCULATIONS IN ACCORDANCE WITH SECTION 403.6.1 FBC-10 | | | ENERGY CONSERVATION. | | | 2) REFER TO SECTION 101.4.3 FBC-10 ENERGY CONSERVATION: | | | ENERGY CALCULATIONS ARE REQUIRED FOR THE NEW ADDITION. | | | PLEASE SUBMIT TWO COPIES OF FORM 402 (PRESCRIPTIVE | | | COMPLIANCE) OR FORM 405 (PERFORMANCE COMPLIANCE)- SEE | | | TABLE 103.2.1. | | | 3) THE ELECTRICAL PLAN INDICATES A BATH EXHAUST FAN. | | | PLEASE SHOW THE FAN AND EXHAUST DUCT DETAILS ON THE | | | MECHANICAL PLAN. | | | 4) PROVIDE DETAILS FOR INSTALLATION OF THE CONDENSER | | | SLAB, AND TIE-DOWN ENGINEERING FOR ANCHORING THE UNIT | | | TO THE SLAB- SECTION M1307.2.1 FBC-10 RESIDENTIAL. | | | 5) REFER TO SECTION 402.4.3 FBC-10 ENERGY CONSERVATION: | | | NEW WOOD-BURNING FIREPLACES SHALL HAVE GASKETED DOORS | | | AND OUTDOOR COMBUSTION AIR. PLEASE REVISE THE PLANS TO | | | SHOW COMPLIANCE. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | |
|