| 2015-06-25 13:24:12 | 6/25/2015 |
| | PROJECT: PRIDDY ADDITION |
| | PERMIT#: 15061007 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW |
| | COMMENTS: |
| | |
| | 1) PROVIDE A COMPLETE ELECTRICAL LOAD SUMMARY |
| | CALCULATION INCLUDING ALL EXISTING ELECTRICAL LOADS AND |
| | IN ADDITION TO THAT INCLUDE THE ADDED LOAD OF THE NEW |
| | ADDITION. NEC 215.5 |
| | |
| | 2) PROVIDE A COMPLETE ELECTRICAL RISER DIAGRAM. |
| | IDENTIFY ALL EXISTING ELECTRICAL CONDUITS SERVICE |
| | ENTRANCE, FEEDERS AND GROUNDING ELECTRODE SYSTEM IN THE |
| | CORRECT LOCATION AT OR PRIOR TO THE IST MEANS OF |
| | DISCONNECT. |
| | |
| | 3) INDICATE THE LOCATION OF THE ELECTRICAL SERVICE, THE |
| | EXISTING ELECTRICAL PANEL AND THE NEW ELECTRICAL |
| | SUB-PANEL. |
| | |
| | 4) VERIFY AND INSTALL SMOKE DETECTORS AS REQUIRED FOR |
| | NEW CONSTRUCTION. WHEN ALTERATIONS, REPAIRS, OR |
| | ADDITIONS REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE |
| | SLEEPING ROOMS ARE ADDED OR CREATED IN EXISTING |
| | DWELLINGS, THE INDIVIDUAL DWELLING UNIT SHALL BE |
| | EQUIPPED WITH SMOKE ALARMS LOCATED AS REQUIRED FOR NEW |
| | DWELLINGS. FBC-RESIDENTIAL 314 AND 315. |
| | |
| | SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| | MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS |
| | ARE REQUIRED FOR SWIMMING POOL, SECURITY, CCTV, |
| | AUDIO/VIDEO, NETWORK, DATA, AND, COMMUNICATION, AS |
| | NEEDED. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |