2015-08-18 17:48:03RESIDENTIAL (R3) ADDITION, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- PROVIDE ENERGY CALCULATIONS (2 COPIES). SEC. 1006 OF
 2010 FBC-ENERGY CONSERVATION.
  
 3- PROVIDE SOIL TEST REPORT. SEC. R401.4 OF 2010
 FBC-RESIDENTIAL.
  
 4- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 REMOVAL OF EXISTING SCREEN ENCLOSURE AT THE NEW
 ADDITION AREA AND PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS FOR THE RE-CONSTRUCTION OF THE SCREEN
 ENCLOSURE AT THE NEW ADDITION AREA. SEC. R301 OF 2010
 FBC-RESIDENTIAL.
  
 5- SHEET A-4: PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS FOR THE CONSTRUCTION OF THE EXTERIOR
 WALL BETWEEN THE NEW ADDITION AND THE EXISTING SCREEN
 ENCLOSURE, INCLUDING COMPLETE DETAILS AND
 SPECIFICATIONS FOR THE NEW POCKET SLIDING GLASS DOORS
 INSTALLATION. SEC. 107.2.1 CITY AMENDMENTS AND SEC.
 R301.
  
 6- SPECIFY CARBON MONOXIDE ALARMS FOR ALL BEDROOMS AS
 REQUIRED BY SEC. R315.
  
 7- SPECIFY GUTTERS AND LEADERS AS REQUIRED BY SEC.
 R318.6.
  
 8- SHEET A-7:
 A) ROOF SHEATHING SIZE AND NAILING SHOWN ON THE GABLE
 END DETAIL, TYPICAL WALL SECTION AND DIAPHRAGM SCHEDULE
 ON SHEET A-5 DON'T MATCH. REVISE AS REQUIRED. SEC.
 107.2.1 CITY AMENDMENTS. ALSO, COORDINATE INFORMATION
 SHOWN ON THE MECHANICAL FASTENER SCHEDULE WITH
 INFORMATION SHOWN ON THE GABLE END DETAIL. NOTE:
 SPECIFY ONLY ONE TYPE OF ROOF SHEATHING NAILS OR
 PROVIDE ENGINEERING FOR NAILS OTHER THAN 8D RING SHANK
 NAILS. CLARIFY WHERE IS THIS GABLE END DETAIL TAKEN AT.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 B) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FO THE
 CONSTRUCTION OF THE MASONRY FIREPLACE SHOWING
 COMPLIANCE WITH SEC. R1001 AND TABLE R1001.1. PROVIDE
 COMPLETE SPECIFICATIONS, SIZES, ETC. FOR ALL COMPONENTS
 (FLUE LINING, HEARTH, MASONRY WALL VERTICAL AND
 HORIZONTAL REINFORCEMENT, CAP BEAM, ETC.) SHOWN ON
 FIREPLACE/CHIMNEY SECTION. AND PROVIDE COMPLETE
 SPECIFICATIONS FOR ALL FRAMING MEMBERS AND FASTENERS.
 SEC. R301.
  
 C) CLEARLY SPECIFY HOW PROVIDING ROOF CROSS VENTILATION
 AS REQUIRED BY SEC. R806. TYPICAL WALL SECTION DOESN'T
 SPECIFY VENTS TYPE, SIZE AND LOCATION AND THERE IS ONE
 WALL LOCATED ON ZERO LOT WHERE NO OPENINGS ARE ALLOWED.
  
 D) TYPICAL WALL SECTION: PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS FOR SOFFIT CONSTRUCTION SHOWING
 COMPLIANCE WITH SEC. R703.1.3.
  
 E) CLARIFY ROOFING MATERIAL. TYPICAL WALL SECTION CALLS
 FOR 5V CRIMP METAL ROOF, WHILE ELEVATIONS CALL FOR ROOF
 SHINGLES. SEC. 107.2.1 CITY AMENDMENTS.
  
 F) PROVIDE CURRENT ICC EVALUATION REPORT FOR THE TYPE
 OF FOAM INSULATION SPECIFIED ON THE TYPICAL WALL
 SECTION. SEC. R316.
  
 G) FOAM INSULATION LOCATION AS SHOWN ON THE TYPICAL L
 WALL SECTION IS INCORRECT.. THE PURPOSE OF THE FOAM
 INSULATION IS TO HAVE AN ATTIC WITHOUT VENTILATION AND
 INSULATION IS LOCATED UNDERNEATH THE ROOF SHEATHING.
 REVISE AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 H) CLARIFY IF ENGINEER IS DESIGNING AN UNVENTED ATTIC
 OR NOT. ATTIC VENT IS SHOWN ON THE TYPICAL WALL
 SECTION. BUT IT ALSO SHOWS SPRAY FOAM INSULATION. SEC.
 R806.
  
 9- BUILDING CROSS SECTION ON SHEET A-6:
 A) SPECIFY LINTEL ABOVE THE TRANSOM WINDOW. SEC. R301.
  
 B) CLARIFY ROOF INSULATION. COORDINATE WITH ITEM 8(H)
 ABOVE. IS ENGINEERING DESIGN AN UNVENTED ATTIC OR
 VENTED ATTIC. SEC. R806.
  
 C) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF THE WOOD FRAMED WALL SHOWN ON THE
 BUILDING CROSS SECTION. SEC. R301. SPECIFY ALL FRAMING
 MEMBERS AND FASTENERS, WALL SHEATHING, DOUBLE VAPOR
 BARRIER, STUCCO THICKNESS. ETC.
  
 D) TYPE OF DOORS SHOWN ON THE SOUTH ELEVATION DON'T
 MATCH TYPE OF DOORS SHOWN ON THE DOOR SCHEDULE.. REVISE
 AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 10- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY
 FAC 61G20.002(33) FOR:
 A) ROOFING FINISH MATERIAL SPECIFIED ON PLANS.
  
 B) SINGLE HUNG WINDOWS AS SPECIFIED ON PLANS..
  
 C) FIXED WINDOWS AS SPECIFIED ON PLANS.
  
 D) POCKET SLIDING GLASS DOORS AS SHOWN ON PLANS.
  
 E) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS. PROVIDE THE FLORIDA PRODUCT APPROVAL COVER PAGE
 AND PAGE SHOWING THE SPECIFIC CONNECTOR OR ENGINEER OF
 RECORD TO LIST THE FLORIDA PRODUCT APPROVAL NEXT TO THE
 SPECIFIED CONNECTOR.
  
 F) ALL PRECAST LINTELS SPECIFIED ON PLANS.
  
 11- ENGINEER OF RECORD TO APPROVE IN WRITING (NOT
 SIGNING AND SEALING) ALL THE PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REPLACE AND REMOVE ANY REVISED DRAWING.
 SUBMIT COPY OF OLD DRAWINGS FOR REFERENCE TO EXPEDITE
 REVIEW.
  