| Plan Review Notes For Permit 15061003 |
| Permit Number |
15061003 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-07-06 19:01:33 | RESIDENTIAL (R3) RE-ROOF SECOND BUILDING REVIEW | | | COMMENTS. | | | CODE: 2010 FBC-RESIDENTIAL | | | | | | 1- ENGINEER TO REVISE THE RAS 117 CALCULATIONS | | | SUBMITTED: | | | A) THIS BUILDING IS LOCATED IN EXPOSURE "D" NO "C". | | | REVISE CALCULATIONS AS REQUIRED. SEC. R301.2.1.4.3 OF | | | 2010 FBC-RESIDENTIAL. | | | | | | B) HEIGHT OF THE BUILDING IS INCORRECT. THIS IS A TWO | | | STORY BUILDING. 14' HEIGHT IS NOT CORRECT. REVISE | | | CALCULATIONS AS REQUIRED. SEC. R301.1 OF 2010 | | | FBC-RESIDENTIAL. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|