| 2015-06-24 14:32:01 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS. | | | CODE: 2010 FBC-RESIDENTIAL | | | | | | 1- FLAT ROOF FLORIDA PRODUCT APPROVAL FL2533-R12: | | | SELECTED ASSEMBLY W-69 DOESN'T MEET THE DESIGN | | | PRESSURES FOR THE CORNER AREAS OF THIS BUILDING. SELECT | | | ANOTHER ASSEMBLY THAT MEETS THE DESIGN PRESSURES OR | | | PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR BASE | | | SHEET NAIL ENHANCEMENT. NOTE: THIS BUILDING IS LOCATED | | | IN EXPOSURE "D". SEC R301.2.1.4.3 OF 2010 | | | FBC-RESIDENTIAL. | | | | | | 2- TU PLUS ROOF TILE UNDERLAYMENT FL5259-R22: | | | SELF-ADHERING UNDERLAYMENTS NEED TO COMPLY WITH THE | | | DESIGN PRESSURES OF ALL ROOF ZONES. CLEARLY IDENTIFY | | | WHICH MAXIMUM DESIGN PRESSURES FROM SEC. 5.6.4 OF | | | FLORIDA PRODUCT APPROVAL IS GOING TO BE INSTALLED TO | | | VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. | | | R301 OF 2010 FBC-RESIDENTIAL. | | | | | | 3- VALUATION WAS UPDATED TO $22,296 AS REQUIRED BY SEC. | | | 109.3 CITY AMENDMENTS. THE PERMIT FEE BALANCE IS | | | $512.58. | | | | | | IF YOU HAVE ANY QUESTION, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] | | | . |
|