| 2015-09-10 09:22:43 | BUILDING PLAN REVIEW |
| | REVISION: 15060985 |
| | PERMIT:14050111 |
| | ADD: 600 OKEECHOBEE BLVD |
| | CONT: NR WINDOWS/ COASTAL CONSTRUCTION |
| | TEL: (561) 630-3770 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | THE PALM BEACH CONVENTION CENTER HILTON HOTEL |
| | CONSTRUCTION OF NEW 400 ROOM HOTEL INCLUDING BALLROOMS, |
| | RESTAURANT(S), MEETING SPACE, POOL DECK AND AMENITIES |
| | |
| | 2ND REVIEW |
| | DATE: THURS. SEPT. 10/ 2015 |
| | ACTION:DENIED. |
| | |
| | 1) THE ALUCOBOND ACM WALL PANELS REQUIRES PRODUCT |
| | APPROVALS AND TESTING REPORTS. PLEASE NOTE THAT THE |
| | PRODUCT APPROVAL NOA : 12-0125.22 |
| | ALUCOBOND PLUS ALUMINUM PANEL WAS SUBMITTED THIS TIME. |
| | THE DESIGNER OF RECORD HAS NOT REVIEWED THIS PRODUCT |
| | AND AFFIXED THEIR SHOP DRAWING STAMP OF APPROVAL. |
| | ACM SHOP DRAWINGS ALSO HAS A NOTE PROVIDE NOA FOR |
| | FASTENERS. |
| | |
| | |
| | |
| | ORIGINAL BUILDING PROVISO |
| | BUILDING APPROVED WITH EXCEPTION! |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. THE CITY OF |
| | WEST PALM BEACH ACCEPTS MIAMI-DADE NOA'S. FLORIDA STATE |
| | APPROVALS AND REPORTS FROM ALL NATIONALLY RECONIZED |
| | AGENCIES. |
| | |
| | 9A) DEFERRED SUBMITTAL UNDER 107.3.4.2 BUT THE |
| | PRESSURES HAVE TO BE INALLIZED BEFORE PERMIT ISSUANCE. |
| | 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41 |
| | COMPONENTS & CLADDING. |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | 9B) DEFERRED SUBMITTAL UNDER 107.3.4.2. 2010 FBC |
| | 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE |
| | REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 |
| | (2) THE ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND |
| | REVIEWING ALL PROJECT DATA, REPORTS, SHOP DRAWINGS |
| | ETC.. |
| | |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |