| Plan Review Notes For Permit 15060981 |
| Permit Number |
15060981 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2015-11-16 07:28:48 | BUILDING PLAN REVIEW | | | REVISION: 15060981 | | | W. P. B. PERMIT: 14050111 | | | ADD: 600 OKEECHOBEE BLVD | | | CONT: N R WINDOWS/ COASTAL | | | TEL: (561)844-1121: ELEANOR CASTELLANOS | | | E-MAIL: | | | | | | | | | | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 4THREVIEW | | | | | | DATE: MON. NOV. 16/ 2015 | | | ACTION: PROVISO | | | | | | THE FRONT ENTRY DOORS TO BE A BREAK-AWAY AS PER NOA | | | 13-0521.14 PAGE 16/21 WHICH SHOWS A HORIZONTAL MIDRAIL. | | | THE LOCKING DEVICE IN THE DOOR CURRENTLY HAS TO BE | | | REMOVED AND NEVER PUT BACK IN THE DOOR. THE OCCUPANT | | | LOAD OF THE ROOMS THESE DOORS SERVE IS GREATER THAN 300 | | | THE 2010 FBC-B 1008.1.9.3(2) LOCKS AND LATCHES ALLOWING | | | LOCKING DEVICE IN ASSMEBLY OCCUPANCY DOORS IS WHEN THE | | | OCCUPANT LOAD IS 300 OR LESS. THE OCCUPANT LOAD FOR | | | THIS ASSEMBLY OCCUAPANCY IS WELL OVER 300. NO LOCKING | | | DEVICES IN THESE DOORS. | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|