Plan Review Notes
Plan Review Notes For Permit 15060981
Permit Number 15060981
Review Stop B
Sequence Number 3
Notes
Date Text
2015-10-19 11:26:01BUILDING PLAN REVIEW
 REVISION: 15060981
 W. P. B. PERMIT: 14050111
 ADD: 600 OKEECHOBEE BLVD
 CONT: N R WINDOWS/ COASTAL
 TEL: (561)844-1121: ELEANOR CASTELLANOS
 E-MAIL:
  
  
  
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 3RD REVIEW
 DATE: MON. OCT. 19/ 2015
 ACTION: DENIED
  
 1) COMPLIED. THIS REVISION IS ONLY THE SHOP DRAWINGS,
 PLEASE PROVIDE THE ARCHITECTURAL SHEETS TO REFLECT ON
 THE RECORD SET OF DRAWINGS THIS CHANGE.
  
 2) THE NR FLOOR PLAN PO1 DOES NOT INDICATE A REVISION
 TAKING PLACE WITH A NUMBERED DELTA SHOWING THE REVISION
 LOCATION. NEITHER DOES THE NARRATIVE, THE NARRATIVE IS
 DATED MARCH 16/2015 BEFORE THIS REVISION WAS SUBMITTED.
 IT IS NOT A RESPONSE TO THE FIRST SET OF COMMENTS.
 PLEASE REMEMBER WE LOOK FOR A COMPLETE PAPER TRAIL, YES
 UNLESS YOU GIVE US THE ACTUAL NOA, NUMBER AND SHEET
 NUMBER WHERE THIS INFORMATION CAN BE FOUND WE ARE NOT
 GOING TO LOOK THROUGH THOUSANDS OF SHEETS OF NOA'S AND
 PLANS TO FIND THE REQUIRED INFORMATION. WE REQUIRE BOTH
 THE ARCHITECTURAL SHEETS AS WELL AS NR SHOP DRAWINGS
 SHEETS TO REFLECT THE CHANGE. IDENTIFIED BY A NUMBERED
 DELTA AND A WRITTEN RESPONSE.
  
 3) COMPLIED. THE LOCATION IS CRITICAL BECAUSE THE FENCE
 AND POOL BARRIERS ARE BEING CONSIDERED TO BE REMOVED ON
 A DIFFERENT REVISION. IF THESE DOORS ARE ON THE POOL
 SIDE OF THE BUILDING THEN THE POOL BARRIER AND GATES
 WILL AGAIN BE REQUIRED, SINCE CHILDREN WOULD BE ABLE TO
 GAIN ENTRY BY WAY OF THE ACUSENSOR AND SLIDING DOOR
 SYSTEM. 2010 FBC-B 424.1.3.1.9.
  
 4) THE LOCATION OF THESE DOORS WILL NEED TO COMPLY WITH
 1008.1.10 OR ONE OF THE EXCEPTIONS. THESE DOORS DO NOT
 INDICATE THE USE OF PANIC OR FIRE EXIT HARDWARE.
 EXCEPTION 1 DOES ALLOW THE MAIN EXIT DOOR IN A A
 OCCUPANCY IF IT IS IN COMPLIANCE WITH 1008.1.9.3 ITEM
 2.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  
 COMMENT FROM 1ST REVIEW.
 THIS REVISION DOES NOT SHOW ON THE DOOR SCHEDULE WHICH
 DOORS THIS DOOR AFFECTS AND ON THE OCCUPANT LOADS OF
 THE FLOOR PLAN. THE 2010
 FBC-B 1008.1.10 REQUIRES EITHER PANIC OR FIRE EXIT
 HARDWARE ON ALL DOORS SERVING AN ASSEMBLY OCCUPANCY
 WITH AN OCCUPANT LOAD OF 50 OR MORE. ADDITIONAL
 INFORMATION IS REQUIRED. 107.2.1.3.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  