2015-08-05 14:06:57600 OKEECHOBEE BOULEVARD
 TRACKING #15060981
 MASTER #15010064
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PLANS DO NOT INDICATE WHERE THE SLIDING GLASS DOORS ARE
 TO BE INSTALLED. PROVIDE FLOOR PLAN AND OCCUPANT LOAD
 ASSOCIATED WITH EGRESS.
  
 DOOR INDICATES THE USE OF A THUMB-TURN STYLE LOCK. HOW
 WILL THIS AFFECT EGRESS?
  
 INSTALLATION SHALL CONFORM TO NFPA 101 SECTION
 7.2.1.9.1.2 WHEREBY THE DOOR ASSEMBLY SHALL BE DESIGNED
 AND INSTALLED SO THAT, WHEN A FORCE IS APPLIED TO THE
 DOOR LEAF ON THE SIDE FROM WHICH EGRESS IS MADE, IT
 SHALL BE CAPABLE OF SWINGING FROM ANY POSITION TO
 PROVIDE FULL USE OF THE REQUIRED WIDTH OF THE OPENING
 IN WHICH IT IS INSTALLED. (SEE 7.2.1.4.)
 A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS
 THAN 1 IN. (25 MM) HIGH ON A CONTRASTING BACKGROUND
 THAT READS AS FOLLOWS SHALL BE LOCATED ON THE EGRESS
 SIDE OF EACH DOOR OPENING: IN EMERGENCY, PUSH TO OPEN
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  