| Plan Review Notes For Permit 15060981 |
| Permit Number |
15060981 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-08-04 16:10:12 | BUILDING PLAN REVIEW | | | REVISION: 15060981 | | | W. P. B. PERMIT: 14050111 | | | ADD: 600 OKEECHOBEE BLVD | | | CONT: N R WINDOWS/ COASTAL | | | TEL: ( | | | E-MAIL: | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 1ST REVIEW | | | DATE: TUES. AUGUST 04/ 2015 | | | ACTION: DENIED | | | | | | 1) THIS REVISION DOES NOT SHOW ON THE DOOR SCHEDULE | | | WHICH DOORS THIS DOOR AFFECTS AND ON THE OCCUPANT LOADS | | | OF THE FLOOR PLAN. THE 2010 | | | FBC-B 1008.1.10 REQUIRES EITHER PANIC OR FIRE EXIT | | | HARDWARE ON ALL DOORS SERVING AN ASSEMBLY OCCUPANCY | | | WITH AN OCCUPANT LOAD OF 50 OR MORE. ADDITIONAL | | | INFORMATION IS REQUIRED. 107.2.1.3. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|