2015-07-07 16:10:596651 NORTH JOG ROAD
 PERMIT #15060978
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PLANS ARE NOT TO SCALE ARE VERY DIFFICULT TO READ.
  
 SUBMIT PRODUCT DATA CUTSHEETS.
  
 PLANS INDICATE WORK TO BE PERFORMED IN THE
 MAINTENANCE/WAREHOUSE BUILDING WHICH IS LOCATED AT A
 DIFFERENT ADDRESS THAN THE PERMIT APPLICATION.
  
 HOW WILL THE COMMUNICATION SYSTEM SPEAKERS BE
 INTEGRATED WITH THE FIRE ALARM SYSTEM TO AVOID SOUND
 INTERFERENCE OF THE FIRE ALARM?
  
 HOW ARE THE MAG LOCKS BEING COORDINATED WITH THE FIRE
 ALARM SYSTEM?
  
 ROUTING CONDUIT OR LOCATING SECURITY EQUIPMENT SUCH AS
 CARD READERS OR CCTV WITHIN A STAIR ENCLOSURE IS NOT
 PERMITTED BY THE LIFE SAFETY CODE.
  
 LEVEL 99 (CONTROL ROOM FLOOR) HAS SECURITY FEATURES
 THAT CONFLICT THE ARCHITECTURAL LIFE SAFETY PLAN AND
 AFFECT FREE EGRESS TO EXIT STAIRS.
  
 A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE COMPLETED
 AT THIS TIME DUE TO LACK OF INFORMATION SUBMITTED ON
 THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED DURING PLAN RESUBMISSION.
  
 DISCLAIMER: REVIEW AND APPROVAL BY THE AHJ SHALL NOT
 RELIEVE THE OWNER, CONTRACTOR, ETC. OF THE
 RESPONSIBILITY OF COMPLIANCE WITH CODE (NFPA 1, SECTION
 1.14.4). FBC SECTION 105.4.1 PERMIT INTENT: A PERMIT
 ISSUED SHALL BE CONSTRUED TO BE A LICENSE TO PROCEED
 WITH THE WORK AND NOT AS AUTHORITY TO VIOLATE, CANCEL,
 ALTER OR SET ASIDE ANY OF THE PROVISIONS OF THE
 TECHNICAL CODES, NOR SHALL ISSUANCE OF A PERMIT PREVENT
 THE BUILDING OFFICIAL FROM THEREAFTER REQUIRING A
 CORRECTION OF ERRORS IN PLANS, CONSTRUCTION OR
 VIOLATIONS OF THIS CODE.
  