Plan Review Notes
Plan Review Notes For Permit 15060978
Permit Number 15060978
Review Stop E
Sequence Number 1
Notes
Date Text
2015-07-07 14:21:177/7/2015
 PROJECT: LOW VOLTAGE. CCTV, ACCESS CONTROL, SOLID WASTE
 PERMIT#: 15060978
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) THE PLANS HAVE NOT BEEN SIGNED BY THE DESIGNER. WPB
 AMENDMENTS TO FBC, 107.2.1 AND FL ADMIN CODE
 61G15-23.002 ENGINEERS
  
 2) PROVIDE AN APPLICATION FROM A CONTRACTOR LICENSED BY
 THE STATE OF FL FOR THE SCOPE OF WORK APPLIED FOR. FL
 SS 489.105
  
 3) PROVIDE MANUFACTURER PRODUCT SUBMITTALS FOR
 EQUIPMENT, COMPONENTS AND CABLES PROPOSED TO BE
 INSTALLED.
  
 4) PROVIDE UL FIRE RATED ASSEMBLIES TO BE USED FOR
 PENATRATION OF FIRE RATED SURFACES.
  
 5) INDICATE THE LOCATION FOR ANY LINE VOLTAGE POWER
 SUPPLIES PROPOSED TO BE INSTALLED. THE INSTALLATION OF
 LINE VOLTAGE CONNECTIONS SHALL BE BY OTHERS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED.
 ADDITIONAL COMMENTS MAY APPEAR IN THE NEXT REVIEW CYCLE
 THAT WERE NOT PART OF THIS REVIEW.
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  