| 2015-08-11 13:48:14 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC 2010 / 2008 NEC |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY ELECTRICAL |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THE UNDERGROUND ELECTRICAL SERVICE LATERALS FOR THE |
| | TWO SINGLE FAMILY STRUCTURES LOCATED ON N STREET CAN |
| | NOT CROSS THROUGH THE ADJACENT PROPERTY CONTAINING THE |
| | TWO SINGLE FAMILY STRUCTURES LOCATED ON GEORGIA AVENUE, |
| | AS SHOWN ON THE ELECTRICAL SITE PLAN E-1, WITHOUT A |
| | RECORDED UTILITY EASEMENT. UTILITY EASEMENTS, EASEMENT |
| | LOCATION AND ASSOCIATED RESTRICTIVE PROPERTY COVENANTS |
| | ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL FOR REVIEW |
| | AND APPROVAL PRIOR TO RECORDING. SAID DOCUMENTS SHALL |
| | BE RECORDED AND PROOF OF RECORDING ON THE PLAT, AND |
| | ACCEPTANCE BY THE CITY SURVEYOR, SHALL BE PROVIDED. |
| | |
| | 2) FBC-R314.3 SMOKE ALARMS SHALL BE INSTALLED IN THE |
| | FOLLOWING LOCATIONS: 3. ON EACH ADDITIONAL STORY OF THE |
| | DWELLING, INCLUDING BASEMENTS AND HABITABLE ATTICS BUT |
| | NOT INCLUDING CRAWL SPACES AND UNINHABITABLE ATTICS. |
| | |
| | 3) IN ADDITION TO THE LIGHTING OUTLET SPECIFIED ON THE |
| | PLANS IN THE ATTIC, PROVIDE A RECEPTACLE OUTLET. FBC-R |
| | - M1305.1.3.1 ELECTRICAL REQUIREMENTS. A LUMINAIRE |
| | CONTROLLED BY A SWITCH LOCATED AT THE REQUIRED |
| | PASSAGEWAY OPENING AND A RECEPTACLE OUTLET SHALL BE |
| | INSTALLED AT OR NEAR THE APPLIANCE LOCATION IN |
| | ACCORDANCE WITH CHAPTER 34. SEE ALSO 2008 NEC 210.63 |
| | |
| | |
| | |