2015-08-10 18:25:36PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SPECIFY THE TYPE OF CONSTRUCTION AN OCCUPANCY TYPE
 ON THE PLANS. FBC 601 AND 302. SINGLE FAMILY HOMES ARE
 OCCUPANCY TYPE R-3 AND CONSTRUCTION TYPE V-B HAS THE
 LEAST RESTRICTIONS.
  
 2) SHEET SP-2 WHICH IS LISTED IN THE DRAWING LIST ON
 SP-1, IS MISSING FROM THE PLANS. FBC 107.2.1
  
 3) SUBMIT ENERGY COMPLIANCE FORMS FOR UNITS A, B AND C
 AS REQUIRED BY FBC ENERGY CONSERVATION 405.3
  
 4) THE TAG FOR THE NEWEL POST AT DETAIL D/A-5.2 SHOULD
 BE E/A-5.2 NOT E/A-15. FBC 107.2.1
  
 5) THE HANDRAIL TAG AND SECTION ON A-5.2 SHOULD BE
 3/A-5.2 NOT 3/A-15. FBC 107.2.1
  
 6) THE WINDOW SCHEDULE IN THE PLANS SPECIFIES DOUBLE
 HUNG WINDOWS AND THE PRODUCT APPROVALS (NOA NO.
 11-1013.14) THAT WERE SUBMITTED ARE FOR SINGLE HUNG
 WINDOWS. FBC 107.2.1
  
 7) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE
 FIXED WINDOWS ( NOA NO. 11-1110.15 ) EXPIRED ON
 FEBRUARY 19, 2014. DCA RULE 9N-3
  
 8) SUBMIT TWO SETS OF PRODUCT APPROVALS THAT HAVE BEEN
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD FOR THE ASPHALT SHINGLE AND METAL ROOF COVERING
 MATERIALS. FBC 107.3.4.1
  
 9) THE GUARD SPACING FOR SEVERAL OF THE PORCH RAILINGS
 ON SHEET A-5.4 DO NOT COMPLY WITH FBC-R312.3 FOR
 REQUIRED GUARDS REJECTING A 4 INCH DIAMETER SPHERE. THE
 PLANS INDICATE THAT THE PORCHES ARE LESS THAN 30 INCHES
 ABOVE GRADE, THEREFORE THE GUARDS ARE NOT REQUIRED AND
 THE SPACING OF THE RAILS ARE NOT REQUIRED TO COMPLY.
  