| 2015-08-10 18:25:36 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC 2010 |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) SPECIFY THE TYPE OF CONSTRUCTION AN OCCUPANCY TYPE |
| | ON THE PLANS. FBC 601 AND 302. SINGLE FAMILY HOMES ARE |
| | OCCUPANCY TYPE R-3 AND CONSTRUCTION TYPE V-B HAS THE |
| | LEAST RESTRICTIONS. |
| | |
| | 2) SHEET SP-2 WHICH IS LISTED IN THE DRAWING LIST ON |
| | SP-1, IS MISSING FROM THE PLANS. FBC 107.2.1 |
| | |
| | 3) SUBMIT ENERGY COMPLIANCE FORMS FOR UNITS A, B AND C |
| | AS REQUIRED BY FBC ENERGY CONSERVATION 405.3 |
| | |
| | 4) THE TAG FOR THE NEWEL POST AT DETAIL D/A-5.2 SHOULD |
| | BE E/A-5.2 NOT E/A-15. FBC 107.2.1 |
| | |
| | 5) THE HANDRAIL TAG AND SECTION ON A-5.2 SHOULD BE |
| | 3/A-5.2 NOT 3/A-15. FBC 107.2.1 |
| | |
| | 6) THE WINDOW SCHEDULE IN THE PLANS SPECIFIES DOUBLE |
| | HUNG WINDOWS AND THE PRODUCT APPROVALS (NOA NO. |
| | 11-1013.14) THAT WERE SUBMITTED ARE FOR SINGLE HUNG |
| | WINDOWS. FBC 107.2.1 |
| | |
| | 7) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE |
| | FIXED WINDOWS ( NOA NO. 11-1110.15 ) EXPIRED ON |
| | FEBRUARY 19, 2014. DCA RULE 9N-3 |
| | |
| | 8) SUBMIT TWO SETS OF PRODUCT APPROVALS THAT HAVE BEEN |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD FOR THE ASPHALT SHINGLE AND METAL ROOF COVERING |
| | MATERIALS. FBC 107.3.4.1 |
| | |
| | 9) THE GUARD SPACING FOR SEVERAL OF THE PORCH RAILINGS |
| | ON SHEET A-5.4 DO NOT COMPLY WITH FBC-R312.3 FOR |
| | REQUIRED GUARDS REJECTING A 4 INCH DIAMETER SPHERE. THE |
| | PLANS INDICATE THAT THE PORCHES ARE LESS THAN 30 INCHES |
| | ABOVE GRADE, THEREFORE THE GUARDS ARE NOT REQUIRED AND |
| | THE SPACING OF THE RAILS ARE NOT REQUIRED TO COMPLY. |
| | |