Plan Review Notes
Plan Review Notes For Permit 15060950
Permit Number 15060950
Review Stop P
Sequence Number 1
Notes
Date Text
2015-07-14 03:39:021) SHOW THE DISTANCE OF THE FLOOR INLETS TO THE
 ADJACENT WALLS. THE SPACING BETWEEN FLOOR INLETS AND
 ADJACENT WALLS SHALL NOT EXCEED 10 FEET PER 2010 FBC
 SEC.424.1.6.5.9.4.
 2) INDICATE ON THE PLANS THAT THE POOL RESTROOMS ARE
 UNDER A SEPARATE PERMIT.
 3) A BACKFLOW PREVENTION DEVICE IS REQUIRED AT THE
 WATER METER FOR THE BUILDING PER THE CITY OF WEST PALM
 BEACH CROSS CONNECTION MANUAL. THE MINIMUM PROTECTION
 REQUIRED AT THE METER IS A DOUBLE CHECK VALVE ASSEMBLY
 AND THE DEVICE MUST BE TESTED BY THE CITY OF WEST PALM
 BEACH UTILITIES DEPT. CONTACT STEPHEN HUNTER AT
 561-822-2242 FOR ADDITIONAL INFORMATION.
 4) AUTOMATIC CHEMICAL FEEDERS SHALL COMPLY WITH
 ANSI/NSF 50 - 2007.
 5) THE SWIMMING POOL WATER CANNOT DISCHARGE TO THE
 CITY'S STORM OR SANITARY SYSTEM PER CITY OF WPB CODE
 CODE OF ORDINANCE SEC. 90-126 (B) (5) AND SEC. 90-203.
 I SUGGEST CONTACTING MANNY GONZALEZ IN THE CITY'S
 ENGINERING DEPT. FOR FURTHER DIRECTION. HE CAN BE
 REACHED AT 561-494-1085.
 6) THE EQUIPMENT AREA SHALL BE SURROUNDED WITH A FENCE
 AT LEAST 4 FEET HIGH AND SHALL COMPLY WITH FBC
 SEC.424.1.5.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  