Plan Review Notes
Plan Review Notes For Permit 15060950
Permit Number 15060950
Review Stop E
Sequence Number 1
Notes
Date Text
2015-08-01 14:51:361ST REVIEW: FBC 2010/NEC 2008
  
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS
  
 PROVIDE FEEDER DETAILS FOR THE NEW ELECTRICAL
 PANELBOARD FOR THE POOL. NEC 215.5
  
 VERIFY THAT ALL FEEDERS FROM THE ELECTRICAL SERVICE
 SOURCE INCLUDE A FULL SIZE INSULATED COPPER EQUIPMENT
 GROUNDING CONDUCTOR SIZED IN ACCORDANCE WITH NEC
 250.22, 680.21, 680.25
  
 SHOW THE LOCATION AND SAFETY CLEARANCES REQUIRED FOR
 THE NEW PANEL BOARD SERVING THE SPA EQUIPMENT. NEC
 110.26
  
 VERIFY ALL SIGHT LIGHTING AND DECORATIVE LIGHTING IS
 GFCI PROTECTED AND LOCATED MORE THAN 5 FEET FROM THE
 POOL AND ABOVE 12 FEET. NEC 680.42, 680.22 (C),
 680.43(B)
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  
  