| Notes |
| Date |
Text |
| 2015-07-08 09:19:14 | RESIDENTIAL (R3) ROOF OVER, SECOND BUILDING REVIEW | | | COMMENTS. | | | CODE: 2010 FBC-RESIDENTIAL | | | | | | 1- TAMKO NOA 12-0716.09 SUBMITTED FOR RECOVERY DECK | | | REQUIRES FASTENERS WITHDRAWAL RESISTANCE TEST (TAS | | | 105). SEE NOTE IN BOLD IN PAGE 17 OF 19 OF NOA | | | SUBMITTED. PROVIDE 2 COPIES OF THE TAS 105 TEST. | | | REQUIRED TO VERIFY THE CALCULATED DESIGN PRESSURES | | | REQUIRED BY SEC. R301 OF 2010 FBC-RESIDENTIAL. | | | THEN, ENGINEER TO REVISE THE RAS 117 CALCULATIONS BASED | | | ON THE TAS 105 RESULTS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|