Plan Review Notes
Plan Review Notes For Permit 15060932
Permit Number 15060932
Review Stop E
Sequence Number 1
Notes
Date Text
2015-07-20 17:13:177/20/2015
 PROJECT: KITCHEN REMODEL
 PERMIT#: 15060935
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC,
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER ONE,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) PROVIDE CODE COMPLIANT PLANS. THE PLANS SUBMITTED
 ARE NOT COMPLIANT IN MANY AREAS OF THE ELECTRICAL AND
 UILDING CODE. SEE THE FOLLOWING LIST OF CODE
 DEFICIENCIES:
 A. REQUIRED OUTLETS MISSING ON PENNINSULA.
 B. OUTLET SPACING REQUIREMENTS NOT MET. ADD REQUIRED
 OUTLETS TO MEET SPACING REQUIREMENTS.
 C. GFCI PROTECTION REQUIRED. ALL OUTLETS FOR KITCHEN
 COUTERTOP REQUIRE GFCI PROTECTION.
 D. AFCI PROTECTION REQUIRED, ALL NEW RECEPTACLES
 REQUIRE AFCI PROTECTION.
 E.TAMPER RESISTANT RECEPTACLES REQUIRED. ALL NEW
 RECEPTACLES SHALL BE TAMPER RESISTANT.
 F. SMOKE DETECTORS REQUIRED, WHEN ALTERATIONS, REPAIRS,
 OR ADDITIONS REQUIRING A PERMIT OCCUR, OR WHEN ONE OR
 MORE SLEEPING ROOMS ARE ADDED OR CREATED IN EXISTING
 DWELLINGS, THE INDIVIDUAL DWELLING UNIT SHALL BE
 EQUIPPED WITH SMOKE ALARMS LOCATED AS REQUIRED FOR NEW
 DWELLINGS.
  
 FOR CODE REFFERENCE PUPOSES REGARDING THE
 AFOREMENTIONED REVIEW DEFICIENCIES, SEE THE NATIONAL
 ELECTRICAL CODE SECTIONS 210.8, 210.52, 406.1 AND THE
 FLORIDA BUILDING CODE - RESIDENTIAL SECTIONS, 314 AND
 315.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  