| Plan Review Notes For Permit 15060930 |
| Permit Number |
15060930 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-08-10 11:43:22 | 8/10/2015 | | | PROJECT: KOCH RESIDENCE | | | PERMIT#: 15060930 | | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC, | | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER ONE, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | 2ND ELECTRICAL PLAN REVIEW | | | ACTION: APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN | | | APPROVED PROVISIONALLY. FAILURE TO CORRECT THE LISTED | | | DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED | | | INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION | | | FEE(S). | | | | | | 1) LUMINAIRES IN CLOTHES CLOSETS SHALL BE INSTALLED IN | | | ACCORDANCE WITH THE PROVISIONS OF THE NEC 410.16(A) AND | | | (B). PROVIDE A NOTE TO INDICATE COMPLIANCE. | | | | | | 2) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER | | | RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11 | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | |
|