| 2015-07-22 11:23:09 | 7/22/2015 |
| | PROJECT: KOCH RESIDENCE |
| | PERMIT#: 15060930 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC, |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER ONE, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW |
| | COMMENTS: |
| | |
| | 1) PROVIDE A FIXTURE SCHEDULE FOR LIGHTING FIXTURES TO |
| | BE INSTALLED INDICATING COMPLIANCE WITH THE NEC |
| | 110.3(B), 410.10(D) AND FBC-ENERGY 502.3.8 |
| | |
| | 2) LUMINAIRES IN CLOTHES CLOSETS SHALL BE INSTALLED IN |
| | ACCORDANCE WITH THE PROVISIONS OF THE NEC 410.16(A) AND |
| | (B). PROVIDE A NOTE TO INDICATE COMPLIANCE. |
| | |
| | 3) VERIFY OR INDICATE COMPLIANCE WITH THE FBC REGARDING |
| | THE EXISTIANCE OR INSTALLATION OF INTERCONNECTED SMOKE |
| | DETECTORS. WHEN ALTERATIONS, REPAIRS, OR ADDITIONS |
| | REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING |
| | ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE |
| | INDIVIDUAL DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE |
| | ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS. |
| | FBC-RESIDENTIAL 314 AND 315 |
| | |
| | 4) INDICATE HOW THE LIGHTING WILL BE CONTROLLLED AND |
| | THE LOCATION OF SWITCHES. INDICATE WHETHER SWITCHES ARE |
| | NEW OR EXISTING. |
| | |
| | 5) INDICATE COMPLIANCE WITH THE NEC. ALL NEW GENERAL |
| | PURPOSE OUTLETS MUST BE TAMPER RESISTANT AND AFCI |
| | PROTECTED. NEC 210.12, 406.11 |
| | |
| | 6) PROVIDE A PANEL SCHEDULE INDICATING COMPLIANCE WITH |
| | THE NEC 210.11(C)(3) AND 408.4 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |