| 2015-07-09 07:22:01 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15060930 |
| | ADD: 525 S. FLAGLER DR. SUITE 7B |
| | CONT: CAMBRIDGE |
| | TEL: (561)784-3722 |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURS. JULY 09/ 2015 |
| | ACTION: DENIED |
| | |
| | 1) PLEASE REVIEW THE ARCHITECTS LETTER AND RECOMMENDED |
| | NOA'S LISTED IN LETTER. BOTH THE SLIDDING GLASS DOOR |
| | AND FIXED WINDOW ARE WIN DOOR PRODUCTS. THE SLIDDING |
| | GLASS DOOR NOA 12-0130.14 AND THE FIXED WINDOW NOA |
| | 14-0916.13. THE SUBMITTED PRODUCT APPROVALS ARE |
| | NEITHER. IF THE NEW PRODUCT APPROVALS ARE TO BE |
| | INSTALLED HAVE THEM REVIEWED BY THE DESIGNER OF RECORD |
| | AND THE LETTER UPDATED AND SIGNED AND SEALED. |
| | |
| | 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 2) THE LETTER FROM ARCHITECT RAYMOND CHLANDY INDICATES |
| | THE WIND DESIGN CRITERIA TO BE 170 VULT, EXPOSURE D, |
| | WIND ZONES 4 & 5 AND GLASS HEIGHT AT 80 FT. THIS |
| | BUILDING IS APPROXIMATELY 32 STORIES TALL AND THE |
| | NEGATIVE PRESSURES ARE TAKEN FROM THE ROOF LINE. |
| | POSITVE PRESSURES BUILD UP FROM GRADE. PLEASE REVIEW |
| | THE NEGATIVE PRESSURES FROM THE HEIGHT OF APPROX. 320 |
| | FT IN HEIGHT. PRESSURES (NEGATIVE) FOR ZONE 4 ARE LOW |
| | AND EXTREMELY LOW FOR ZONE 5. |
| | |
| | 3) ON THE SUBMITTED NOA 14-0807.18 EGS ATLANTIC |
| | ALUMINUM SLIDING GLASS DOORS ENGINEERING SHEETS 3 OF 8, |
| | THE PRESSURES ARE MEASURED ON THE PANEL WIDTH AND |
| | HEIGHT OF DOORS, CIRCLE BOTH, TYPE OF GLAZING, AND |
| | ASSOCIATED PRESSURES. ALSO NOTE ENGINEERING SHEET 2 THE |
| | LIMITING FACTOR IS THE SILL HEIGHT, CIRCLE SILL HEIGHT |
| | ALSO. TO BE REVIEWED BY THE DESIGNER OF RECORD. |
| | |
| | 4) FOR THE FIXED WINDOWS NOA 12-1005.01 PGT SS 3500 |
| | ALUMINUM STOREFRONT WAS SUBMITTED. PLEASE IDENTIFY THE |
| | SYSTEM TO BE INSTALLED BY TABLE, PANEL WIDTH AND |
| | HEIGHT. |
| | TYPE OF GLAZING, AND ASSOCIATED PRESSURES. TO BE |
| | REVIEWED BY THE DESIGNER OF RECORD. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |