Plan Review Notes
Plan Review Notes For Permit 15060930
Permit Number 15060930
Review Stop B
Sequence Number 1
Notes
Date Text
2015-07-09 07:22:01BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15060930
 ADD: 525 S. FLAGLER DR. SUITE 7B
 CONT: CAMBRIDGE
 TEL: (561)784-3722
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. JULY 09/ 2015
 ACTION: DENIED
  
 1) PLEASE REVIEW THE ARCHITECTS LETTER AND RECOMMENDED
 NOA'S LISTED IN LETTER. BOTH THE SLIDDING GLASS DOOR
 AND FIXED WINDOW ARE WIN DOOR PRODUCTS. THE SLIDDING
 GLASS DOOR NOA 12-0130.14 AND THE FIXED WINDOW NOA
 14-0916.13. THE SUBMITTED PRODUCT APPROVALS ARE
 NEITHER. IF THE NEW PRODUCT APPROVALS ARE TO BE
 INSTALLED HAVE THEM REVIEWED BY THE DESIGNER OF RECORD
 AND THE LETTER UPDATED AND SIGNED AND SEALED.
  
 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 2) THE LETTER FROM ARCHITECT RAYMOND CHLANDY INDICATES
 THE WIND DESIGN CRITERIA TO BE 170 VULT, EXPOSURE D,
 WIND ZONES 4 & 5 AND GLASS HEIGHT AT 80 FT. THIS
 BUILDING IS APPROXIMATELY 32 STORIES TALL AND THE
 NEGATIVE PRESSURES ARE TAKEN FROM THE ROOF LINE.
 POSITVE PRESSURES BUILD UP FROM GRADE. PLEASE REVIEW
 THE NEGATIVE PRESSURES FROM THE HEIGHT OF APPROX. 320
 FT IN HEIGHT. PRESSURES (NEGATIVE) FOR ZONE 4 ARE LOW
 AND EXTREMELY LOW FOR ZONE 5.
  
 3) ON THE SUBMITTED NOA 14-0807.18 EGS ATLANTIC
 ALUMINUM SLIDING GLASS DOORS ENGINEERING SHEETS 3 OF 8,
 THE PRESSURES ARE MEASURED ON THE PANEL WIDTH AND
 HEIGHT OF DOORS, CIRCLE BOTH, TYPE OF GLAZING, AND
 ASSOCIATED PRESSURES. ALSO NOTE ENGINEERING SHEET 2 THE
 LIMITING FACTOR IS THE SILL HEIGHT, CIRCLE SILL HEIGHT
 ALSO. TO BE REVIEWED BY THE DESIGNER OF RECORD.
  
 4) FOR THE FIXED WINDOWS NOA 12-1005.01 PGT SS 3500
 ALUMINUM STOREFRONT WAS SUBMITTED. PLEASE IDENTIFY THE
 SYSTEM TO BE INSTALLED BY TABLE, PANEL WIDTH AND
 HEIGHT.
 TYPE OF GLAZING, AND ASSOCIATED PRESSURES. TO BE
 REVIEWED BY THE DESIGNER OF RECORD.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  