2015-07-28 15:43:581ST REVIEW: FBC 2010 MECHANICAL
 REVISION PERMIT #15060928/ MASTER PERMIT #15020476
 7/28/15
  
 1) PROVIDE VENTILATION CALCULATIONS FOR THE WET DEPOT
 AND DRY DEPOT EXTENSIONS IN ADDITIONS IN ACCORDANCE
 WITH TABLE 403.3 FBC-10 MECHANICAL.
 2) SHOWS A MEANS OF VENTILATION FOR THE WET DEPOT
 ADDITION- SECTION 401.2.
 3) PROVIDE EQUIPMENT SCHEDULES ON THE PLANS FOR
 AU'S-25, 26, 27, 28,29 & 30. LIST THE MODEL NUMBERS,
 COOLING CAPACITIES, REFRIGERANT TYPES AND AMOUNTS IN
 LBS, EFFICIENCY RATINGS, AND ELECTRICAL DATA.
 4) SHEET RE3.1 SHOWS REFRIGERANT LEAK DETECTORS AT EACH
 AU LOCATION: A) PROVIDE EQUIPMENT SCHEDULES ON THE PLAN
 FOR THE DEVICES. B) INDICATE COMPLIANCE WITH SECTIONS
 1105.6, 1105.6.3, AND 1105.6.4- VENTILATION
 CALCULATIONS FOR NORMAL AND EMERGENCY CONDITIONS. C)
 SHOW THE LOCATIONS OF ALL MECHANICAL COMPONENTS OF THE
 VENTILATION SYSTEMS ON THE PLANS AND INCLUDE EQUIPMENT
 SCHEDULES. D) PROVIDE A SEQUENCE OF OPERATION NARRATIVE
 AND DIAGRAM ON THE PLAN CLARIFYING HOW LEAK DETECTON
 WILL ACTIVATE THE EMERGENCY VENTILATION SYSTEM.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  