| 2015-08-19 17:58:33 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE |
| | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO |
| | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE |
| | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. |
| | |
| | PAGE SE-1 |
| | 1. ADD A NOTE TO SPECIFY THAT ?UNLESS PRIOR |
| | ARRANGEMENTS ARE MADE WITH THE ELECTRICAL INSPECTOR, |
| | ALL TRENCHING SHALL REMAIN OPEN FOR INSPECTION. NO SITE |
| | TUBES WILL BE ALLOWED.? |
| | PAGE E-1.0 |
| | 1. NOTE 4 ON PAGE E1 SHALL BE CORRECTED TO MATCH CODE |
| | DICTION. |
| | 2. THE APPLICABLE CODE IS THE 2008 EDITION OF THE NEC, |
| | NOT THE 2002. SERIES RATING IS ADDRESSED IN SECTION |
| | 240.86 OF THE APPLICABLE CODE. |
| | PAGE E-3.0 |
| | 1. MISSING EXIT/EGRESS LIGHT. |
| | 2. MISSING EXIT/EGRESS LIGHT. |
| | PAGE E-4.0 |
| | 1. PANEL H11-1 CKT 37/39/41 TO READ T11 & P11. |
| | 2. PANEL H12-1 CKT 37/39/41 TO READ T12 & P12. |
| | 3. PANEL H10-1 CKT 37/39/41 TO READ T14 & P14. |
| | 4. LIGHTING CONTROL SCHEDULE H9 DOES NOT MATCH PANEL |
| | SCHEDULE ABOVE. |
| | 5. LIGHTING CONTROL SCHEDULE H10 DOES NOT MATCH PANEL |
| | SCHEDULE ABOVE. |
| | 6. LIGHTING CONTROL SCHEDULE H11 DOES NOT MATCH PANEL |
| | SCHEDULE ABOVE. |
| | 7. LIGHTING CONTROL SCHEDULE H12 DOES NOT MATCH PANEL |
| | SCHEDULE ABOVE. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU |
| | |