| Plan Review Notes For Permit 15060911 |
| Permit Number |
15060911 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-07-07 11:26:58 | 1ST REVIEW: FBC 2010 MECHANICAL | | | | | | 1) ENERGY COMPLIANCE FORM 506-2010: A) THE CONSTRUCTION | | | MATERIALS LISTED FOR THE LOADING DOCK WALLS IN THE | | | INPUT DATA REPORT SHOW SOLID WALLS WHICH DOES NOT MATCH | | | THE PLAN WHICH SHOWS SEVEN INSULATED ROLL-UP DOORS. B) | | | THE REPORT IS LISTING ONLY TWO MAN DOORS HOWEVER THERE | | | ARE THREE SHOWN ON THE PLAN. | | | 2) THE AIR SYSTEM SIZING SUMMARIES INDICATE THE | | | LOCATION OF THE PROJECT TO BE IN MIAMI. PLEASE REVISE | | | THE CALCS TO INDICATE WEST PALM BEACH LOCATION, AND USE | | | THE CORRECT DB/WB TEMPERATURES PER TABLE 1A MANUAL N. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|