| 2015-06-18 15:14:59 | APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN APPROVED |
| | PROVISIONALLY. FAILURE TO CORRECT THE LISTED |
| | DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED |
| | INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION |
| | FEE(S). |
| | |
| | 1) WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A |
| | PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE |
| | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS |
| | LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL |
| | 314 AND 315. |
| | |
| | 2) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER |
| | RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11 |
| | |
| | 3) IN ADDITION TO THE NUMBER OF BRANCH CIRCUITS |
| | REQUIRED BY OTHER PARTS OF THIS SECTION, AT LEAST ONE |
| | 20-AMPERE BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY |
| | BATHROOM RECEPTACLE OUTLET(S). SUCH CIRCUITS SHALL HAVE |
| | NO OTHER OUTLETS. NEC 210.11(C)(3) |
| | |
| | 4) ALL 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE |
| | RECEPTACLES INSTALLED IN THE LOCATIONS SPECIFIED IN (1) |
| | THROUGH (8) SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER |
| | PROTECTION FOR PERSONNEL. NEC 210.8 (1) BATHROOMS |
| | |
| | 5) IN DWELLING UNITS, AT LEAST ONE RECEPTACLE OUTLET |
| | SHALL BE INSTALLED IN BATHROOMS WITHIN (3 FT) OF THE |
| | OUTSIDE EDGE OF EACH BASIN. NEC 210.52 (D) |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |