Plan Review Notes
Plan Review Notes For Permit 15060823
Permit Number 15060823
Review Stop B
Sequence Number 1
Notes
Date Text
2015-06-19 09:30:25 
 BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15060823
 ADD: 403 S. SAPODILLA AVE. SUITE # 313
 CONT: ROBERT KEATING INC.
 TEL: (561)239-9694
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. JUNE 19/2015
 ACTION: DENIED
  
 1) PLEASE PROVIDE THE AMOUNT OF STORIES/ FLOORS IN THIS
 BUILDING SO BUILDING CONSTRUCTION TYPE CAN BE
 DETERMINED.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.:
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING / BUILDING TYPE
  
 2) TO DATE THE SLAB THICKNESS HAS NOT BEEN DETERMINED,
 TESTING HAS TO BE FOR A 6 INCH SLAB. PLEASE ALSO NOTE
 THAT THE SUBMITTED TEST FOR PROFLEX 90 IS TESTED WITH
 DROP CEILINGS. TEST REPORTS CAN NOT CONTAIN DROPPED
 CEILINGS. TEST NEED TO COMPLY TO THE FOLLOWING CODE
 SECTIONS:
  
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION
  
 2A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 2B) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 2C) FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 TYPE III-TYPE V CONSTRUCTION:
 719.2 CONCEALED INSTALLATION.
 INSULATING MATERIALS, WHERE CONCEALED AS INSTALLED IN
 BUILDINGS OF ANY TYPE OF CONSTRUCTION, SHALL HAVE A
 FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A
 SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450.
  
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP