Plan Review Notes
Plan Review Notes For Permit 15060822
Permit Number 15060822
Review Stop P
Sequence Number 1
Notes
Date Text
2015-07-11 09:36:531) INDICATE THE DIAMETER OF THE DOWNSPOUTS THAT ARE
 LOCATED IN THE COLUMNS AND SHOW THE SQUARE FOOTAGE
 DRAINED BY EACH DOWNSPOUT. THE DOWNSPOUTS SHALL BE
 SIZED IN ACCORDANCE WITH TABLE 1106.2 (1).
 THE SIZING SHALL BE BASED ON A PROJECTED RAINFALL RATE
 OF 5 INCHES PER HOUR,
 2) THE PLAN SHOWS THE DOWNSPOUT DISCHARGING ABOVE
 GRADE. THE LOCARION / TERMINATION OF THE DISCHARGE
 SHALL NOT CAUSE A NUISANCE TO PEDESTRIANS. THE
 DOWNSPOUTS SHALL DRAIN INTO A SEPARATE STORM SEWER
 SYSTEM OR TO AN APPROVED PLACE OF DISPOSAL. 2010 FPC
 SEC.1101.2.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR