| Plan Review Notes For Permit 15060814 |
| Permit Number |
15060814 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-06-25 13:04:53 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | THE LOCATION OF THE NORTH FDC AND FIRE HYDRANT IS NOT | | | LOCATED IN AN ACCEPTABLE LOCATION FOR ARRIVING AND | | | WORKING FIRE APPARATUS. | | | | | | THE LOCATION OF THE FDC AND FIRE HYDRANT IS RECOMMENDED | | | TO BE MOVED NORTH TO AN AREA BY THE FIRE COMMAND ROOM | | | ALONG THE DROP OFF ACCESS ROAD. | | | | | | REFERENCES TO SHEETS NOT CONTAINED IN THIS PACKET CAN | | | NTO BE CONFIRNMED AND ARE NOT APPROVED, SPECIFICALLY | | | SHEET 5.02 SHOWING THE LOCATION OF FDC AND FIRE HYDRANT | | | # 2. |
|