| Plan Review Notes For Permit 15060795 |
| Permit Number |
15060795 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2015-11-23 14:05:02 | 11/23/15 ON MALBARRAN'S DESK. CP | | 2015-11-17 08:57:43 | 3RD REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15060795 | | | 11/17/15 | | | | | | 1) SHEET M1, BUILDING #3: THE EXHAUST FAN AT 150 CFM IN | | | THE GROOMING AREA MUST BE A MINIMUM OF 202 CFM PER | | | TABLE 403.3 ( 225 SF. X .9 CFM/SF.) | | | 2) M1: PLEASE NUMBER THE BUILDINGS TO MATCH THE FLOOR | | | PLANS AND PROVIDE THE CFM'S AT EACH SUPPLY DIFFUSER | | | LOCATION SHOWN ON THE MECHANICAL PLANS FOR BUILDINGS #1 | | | & #2. | | | 3) M2: THE VENTILATION CALCULATIONS ARE INCOMPLETE. THE | | | EXISTING AC SYSTEMS MUST BE CAPABLE OF PROVIDING THE | | | REQUIRED OUTDOOR AIR FOR OCCUPANTS AS INDICATED IN | | | TABLE 403.3: (7.5 CFM PER OCCUPANT + .18 CFM/SF). | | | INDICATE ON THE SCHEDULES THE TOTAL SUPPLY AIR CFM'S OF | | | EACH AIR HANDLER, AND THE TOTAL OUTDOOR AIR BEING | | | SUPPLIED. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|