2015-11-23 14:05:0211/23/15 ON MALBARRAN'S DESK. CP
2015-11-17 08:57:433RD REVIEW: FBC 2014 MECHANICAL
 PERMIT #15060795
 11/17/15
  
 1) SHEET M1, BUILDING #3: THE EXHAUST FAN AT 150 CFM IN
 THE GROOMING AREA MUST BE A MINIMUM OF 202 CFM PER
 TABLE 403.3 ( 225 SF. X .9 CFM/SF.)
 2) M1: PLEASE NUMBER THE BUILDINGS TO MATCH THE FLOOR
 PLANS AND PROVIDE THE CFM'S AT EACH SUPPLY DIFFUSER
 LOCATION SHOWN ON THE MECHANICAL PLANS FOR BUILDINGS #1
 & #2.
 3) M2: THE VENTILATION CALCULATIONS ARE INCOMPLETE. THE
 EXISTING AC SYSTEMS MUST BE CAPABLE OF PROVIDING THE
 REQUIRED OUTDOOR AIR FOR OCCUPANTS AS INDICATED IN
 TABLE 403.3: (7.5 CFM PER OCCUPANT + .18 CFM/SF).
 INDICATE ON THE SCHEDULES THE TOTAL SUPPLY AIR CFM'S OF
 EACH AIR HANDLER, AND THE TOTAL OUTDOOR AIR BEING
 SUPPLIED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  