| Plan Review Notes For Permit 15060795 |
| Permit Number |
15060795 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-10-08 10:07:55 | 2ND REVIEW: FBC 2010 MECHANICAL | | | PERMIT #15060795 | | | 10/8/15 | | | | | | 1) THE HVAC PLAN DOES NOT MEET COMPLIANCE PER TABLE | | | 404.3 FBC-10 MECHANICAL. AS STATED IN THE 1ST REVIEW | | | EXHAUST AIR AT A RATE OF .90 CFM PER SQ. FT. IS | | | REQUIRED AND THE RECIRCULATION OF AIR FROM THE SPACES | | | CANNOT BE RECIRCULATED PER FOOTNPOTE B. THE PLAN DOES | | | NOT INDICATE A SYSTEM OF "AIR IN AND AIR OUT" AS | | | REQUIRED, AND ALSO INDICATES RETURN AIR FROM THE ANIMAL | | | AREAS BEING RECIRCULATED. FURTHER, PLEASE NOTE THAT THE | | | FANTECH ERV'S SPECIFIED AND SHOWN ON THE PLANS ARE | | | DESIGNED FOR HEAT EXCHANGE IN RESIDENTIAL OCCUPANCIES, | | | AND AS SHOWN IN THE DIAGRAMS, ARE NOT PROVIDING THE | | | NECESSARY EXHAUST. | | | 2) THE VENTILATION CALCULATIONS ARE NOT INDICATING THE | | | REQUIRED O/A FOR OCCUPANTS AS PREVIOSULY REQUESTED IN | | | THE1ST REVIEW- REFER TO TABLE 403.3: 7.5 CFM PER | | | OCCUPANT + 0.18 PER SQ. FT. OF THE SPACE. | | | 3) AT THIS TIME I AM REQUESTING THAT A MEETING BE | | | ARRANGED BETWEEN THE DESIGN PROFESSIOANLS AND MYSELF IN | | | AN EFFORT TO HELP CLARIFY THE CODE REQUIREMENTS AND | | | EXPEDITE THE REVIEW PROCESS. MY CONTACT INFORMATION IS | | | PRINTED BELOW. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|