2015-10-27 16:37:19THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE2008 EDITION
 OF THE NEC, (NATIONAL ELECTRICAL CODE); 2010 EDITION OF
 THE FBC, (FLORIDA BUILDING CODE) AS APPLICABLE AND
 BELOW ARE THE DEFICIENCIES NOTED.
  
 1. BLDG. 1:
 A) PER NEC, THE RESTROOM SHALL HAVE A LIGHT CONTROLLED
 VIA A WALL SWITCH. PER FBC-ENERGY CONSERVATION CODE,
 THAT SWITCH SHALL BE MOTION ACTIVATED.
 B) EXIT/EMERGENCY LIGHT COMBO REQUIRED ABOVE THE EXIT
 DOORWAY AND INSIDE THE WORKROOM.
 C) NEC 600.5 REQUIRES THAT THERE BE A DEDICATED SIGN
 OUTLET AT EVERY PEDESTRIAN ENTRY IN EVERY COMMERCIAL
 ESTABLISHMENT.
 2. BLDG. 2
 A) NEC 600.5 REQUIRES THAT THERE BE A DEDICATED SIGN
 OUTLET AT EVERY PEDESTRIAN ENTRY IN EVERY COMMERCIAL
 ESTABLISHMENT.
 B) EXIT/EMERGENCY LIGHT COMBO REQUIRED ABOVE THE EXIT
 DOORWAY.
 C) EXIT LIGHT REQUIRED AT THE END OF THE CORRIDORS
 W/ARROW TOWARDS EXIT DOORWAY.
 D) EMERGENCY LIGHTS REQUIRED MIDWAY IN THE CORRIDORS.
 E) NEC 110.26(D) REQUIRES PROPER ILLUMINATION ABOUT
 ELECTRICAL EQUIPMENT. THIS ILLUMINATION SHALL NOT BE
 CONTROLLED BY AUTOMATIC MEANS.
 3. BLDG. 3:
 A) NEC 600.5 REQUIRES THAT THERE BE A DEDICATED SIGN
 OUTLET AT EVERY PEDESTRIAN ENTRY IN EVERY COMMERCIAL
 ESTABLISHMENT.
 B) NEC 422.52 REQUIRES THAT THE OUTLET FOR THE ELECTRIC
 DRINKING FOUNTAIN BE PROTECTED WITH GFI.
 C) EXIT/EMERGENCY LIGHT COMBO REQUIRED ABOVE THE EXIT
 DOORWAY.
 D) EXIT/EMERGENCY LIGHT COMBO REQUIRED IN HALL AND IN
 EACH ENCLOSED ROOM AT EITHER END OF HALLWAY.
 4. GENERAL:
 A) ALL LIGHTING SHALL COMPLY WITH ALL THE REQUIREMENTS
 OF THE FBC-ENERGY CONSERVATION CODE.
 B) CORRECT ALL THE LOAD CALCS TO MATCH THE ADDED LOADS.
 C) CORRECT CIRCUIT DIRECTORIES TO MATCH ADDED DEVICES
 AND COMMENTS PER THIS REVIEW.
 D) CORRECT THE FEEDER DIAGRAM REQUIRED BY NEC 215.5
 CONDUCTOR SIZING TO MATCH THE PANEL CONNECTED LOADS.
 E) ALL PANELBOARDS SHALL BE MARKED WITH THE ARC-FLASH
 HAZARD WARNING LABEL AS REQUIRED IN NEC 110.16.
 F) YOU HAD BETTER EMERGENCY LIGHT LAYOUT ON THE
 PREVIOUSLY SUBMITTED PAGE EP 1. USE THAT AS A GUIDE FOR
 YOUR RESUBMITTAL.
  
 THE PLANS SHALL BE REVISED TO ADDRESS THE HEREIN
 MENTIONED ITEMS; ONCE CORRECTED SHALL BE RESUBMITTED
 FOR ANOTHER REVIEW. WHEN RESUBMITTING, YOU ARE REQUIRED
 TO PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM ALONG
 WITH THE STANDARD CITY RE-SUBMITTAL FORM. PLEASE,
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE SUBMITTAL
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARISON. CLOUDING THE CHANGES WILL BE GREATLY
 APPRECIATED.
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
  