| Date |
Text |
| 2015-10-27 16:37:19 | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE2008 EDITION |
| | OF THE NEC, (NATIONAL ELECTRICAL CODE); 2010 EDITION OF |
| | THE FBC, (FLORIDA BUILDING CODE) AS APPLICABLE AND |
| | BELOW ARE THE DEFICIENCIES NOTED. |
| | |
| | 1. BLDG. 1: |
| | A) PER NEC, THE RESTROOM SHALL HAVE A LIGHT CONTROLLED |
| | VIA A WALL SWITCH. PER FBC-ENERGY CONSERVATION CODE, |
| | THAT SWITCH SHALL BE MOTION ACTIVATED. |
| | B) EXIT/EMERGENCY LIGHT COMBO REQUIRED ABOVE THE EXIT |
| | DOORWAY AND INSIDE THE WORKROOM. |
| | C) NEC 600.5 REQUIRES THAT THERE BE A DEDICATED SIGN |
| | OUTLET AT EVERY PEDESTRIAN ENTRY IN EVERY COMMERCIAL |
| | ESTABLISHMENT. |
| | 2. BLDG. 2 |
| | A) NEC 600.5 REQUIRES THAT THERE BE A DEDICATED SIGN |
| | OUTLET AT EVERY PEDESTRIAN ENTRY IN EVERY COMMERCIAL |
| | ESTABLISHMENT. |
| | B) EXIT/EMERGENCY LIGHT COMBO REQUIRED ABOVE THE EXIT |
| | DOORWAY. |
| | C) EXIT LIGHT REQUIRED AT THE END OF THE CORRIDORS |
| | W/ARROW TOWARDS EXIT DOORWAY. |
| | D) EMERGENCY LIGHTS REQUIRED MIDWAY IN THE CORRIDORS. |
| | E) NEC 110.26(D) REQUIRES PROPER ILLUMINATION ABOUT |
| | ELECTRICAL EQUIPMENT. THIS ILLUMINATION SHALL NOT BE |
| | CONTROLLED BY AUTOMATIC MEANS. |
| | 3. BLDG. 3: |
| | A) NEC 600.5 REQUIRES THAT THERE BE A DEDICATED SIGN |
| | OUTLET AT EVERY PEDESTRIAN ENTRY IN EVERY COMMERCIAL |
| | ESTABLISHMENT. |
| | B) NEC 422.52 REQUIRES THAT THE OUTLET FOR THE ELECTRIC |
| | DRINKING FOUNTAIN BE PROTECTED WITH GFI. |
| | C) EXIT/EMERGENCY LIGHT COMBO REQUIRED ABOVE THE EXIT |
| | DOORWAY. |
| | D) EXIT/EMERGENCY LIGHT COMBO REQUIRED IN HALL AND IN |
| | EACH ENCLOSED ROOM AT EITHER END OF HALLWAY. |
| | 4. GENERAL: |
| | A) ALL LIGHTING SHALL COMPLY WITH ALL THE REQUIREMENTS |
| | OF THE FBC-ENERGY CONSERVATION CODE. |
| | B) CORRECT ALL THE LOAD CALCS TO MATCH THE ADDED LOADS. |
| | C) CORRECT CIRCUIT DIRECTORIES TO MATCH ADDED DEVICES |
| | AND COMMENTS PER THIS REVIEW. |
| | D) CORRECT THE FEEDER DIAGRAM REQUIRED BY NEC 215.5 |
| | CONDUCTOR SIZING TO MATCH THE PANEL CONNECTED LOADS. |
| | E) ALL PANELBOARDS SHALL BE MARKED WITH THE ARC-FLASH |
| | HAZARD WARNING LABEL AS REQUIRED IN NEC 110.16. |
| | F) YOU HAD BETTER EMERGENCY LIGHT LAYOUT ON THE |
| | PREVIOUSLY SUBMITTED PAGE EP 1. USE THAT AS A GUIDE FOR |
| | YOUR RESUBMITTAL. |
| | |
| | THE PLANS SHALL BE REVISED TO ADDRESS THE HEREIN |
| | MENTIONED ITEMS; ONCE CORRECTED SHALL BE RESUBMITTED |
| | FOR ANOTHER REVIEW. WHEN RESUBMITTING, YOU ARE REQUIRED |
| | TO PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM ALONG |
| | WITH THE STANDARD CITY RE-SUBMITTAL FORM. PLEASE, |
| | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE SUBMITTAL |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARISON. CLOUDING THE CHANGES WILL BE GREATLY |
| | APPRECIATED. |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | |