| Notes |
| Date |
Text |
| 2015-07-12 09:52:38 | 1) THE COVERSHEET NOTES THIS AS AN ASSEMBLY OCCUPANCY. | | | PLEASE REFER TO 2010 FBC SEC.304. THIS SHOULD BE | | | DEFINED AS A BUSINESS OCCUPANCY. | | | 2) SHT.A-3 - SHOW THE CLEAR INSIDE WIDTH OF THE TOILET | | | ROOM. THE MINIMUM WIDTH SHALL BE 85 INCHES IF BUILT | | | PERFECT, 86 INCHES ALLOWS FOR TOLERANCES. 2010 | | | FBC-ACCESSIBILITY SECS.604 & 606.2. | | | 3) A DRINKING FOUNTAIN IS REQUIRED IN A BUSINESS | | | OCCUPANCY. INDICATE IF BUILDING #3 HAS AN EXISTING | | | DRINKING FOUNTAIN.TABLE 403.1 OF 2010 FPC. | | | 4) SUBMIT A WATER RISER FOR REVIEW. WPB AMEND. TO FBC | | | 107.3.5.1.3. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|