Plan Review Notes
Plan Review Notes For Permit 15060795
Permit Number 15060795
Review Stop P
Sequence Number 1
Notes
Date Text
2015-07-12 09:52:381) THE COVERSHEET NOTES THIS AS AN ASSEMBLY OCCUPANCY.
 PLEASE REFER TO 2010 FBC SEC.304. THIS SHOULD BE
 DEFINED AS A BUSINESS OCCUPANCY.
 2) SHT.A-3 - SHOW THE CLEAR INSIDE WIDTH OF THE TOILET
 ROOM. THE MINIMUM WIDTH SHALL BE 85 INCHES IF BUILT
 PERFECT, 86 INCHES ALLOWS FOR TOLERANCES. 2010
 FBC-ACCESSIBILITY SECS.604 & 606.2.
 3) A DRINKING FOUNTAIN IS REQUIRED IN A BUSINESS
 OCCUPANCY. INDICATE IF BUILDING #3 HAS AN EXISTING
 DRINKING FOUNTAIN.TABLE 403.1 OF 2010 FPC.
 4) SUBMIT A WATER RISER FOR REVIEW. WPB AMEND. TO FBC
 107.3.5.1.3.
  