| Plan Review Notes For Permit 15060795 |
| Permit Number |
15060795 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-07-06 16:49:56 | 1ST REVIEW: FBC 2010 MECHANICAL | | | PERMIT #15060795 7/6/15 | | | | | | 1) REVISE THE PLANS AND THE PERMIT APPLICATION WORK | | | DESCRIPTION TO INDICATE THE ACTUAL SCOPE OF THE | | | PROPOSED PROJECT- NEW PET BOARDING BUSINESS. PLEASE | | | REFERENCE SECTION 901.2 FBC- EXISTING BUILDING CODE AND | | | REVISE THE DESIGN CRITERIA AND PLANS TO BE IN | | | COMPLIANCE WITH ALL THE APPLICABLE REQUIREMENTS LISTED | | | IN CHAPTER 9. | | | 2) REFERENCE SECTION 909.1 FBC-10 EXISTING BUILDING | | | CODE FOR SPECIFIC MECHANICAL COMPLIANCE: PROVIDE | | | MINIMUM VENTILATION CALCULATIONS ON THE PLAN INCLUDING | | | THE REQUIRED OUTSIDE AIR AND REQUIRED EXHAUST RATES PER | | | TABLE 403.3 FBC-10 MECHANICAL. PLEASE NOTE THAT .9 CFM | | | PER SF IS THE REQUIRED RATE OF EXHAUST FOR ALL ANIMAL | | | ROOMS AND SPACES PER THE TABLE, AND THE AIR EXHAUSTED | | | FROM THOSE AREAS SHALL NOT BE RECIRCULATED PER FOOTNOTE | | | B. IN ADDITION, ALL AIR SUPPLIED (100 %) TO SUCH SPACES | | | SHALL BE EXHAUSTED INCLUDING ANY AIR IN EXCESS OF THAT | | | REQUIRED BY TABLE 403.3- REFERENCE SECTION 403.2.1. THE | | | SUBMITTED MECHANICAL PLAN INDICATING NO WORK TO BE DONE | | | IS DEFICIENT. NEW REVISED PLANS, DETAILS, AND | | | SPECIFICATIONS MEETING COMPLIANCE WITH THE ABOVE | | | REQUIREMENTS MUST BE SUBMITTED FOR REVIEW. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|